Toshiba MD-VNK802HEXE Service Manual page 50

Table of Contents

Advertisement

CODE No.
U1 U2 U3 U4
10
20
30
40 Detection pressure of high-pressure sensor (Pd)
11
21
31
41 Detection pressure of low-pressure sensor (Ps)
12
22
32
42 Discharge temperature of compressor 1 (Td1)
13
23
33
43 Discharge temperature of compressor 2 (Td2)
14
24
34
-
Discharge temperature of compressor 3 (Td3)
15
25
35
45 Suction Temperature (TSA)
16
26
36
46 Coil Temperature 1 (TE1)
17
27
37
-
Coil Temperature 2 (TE2)
18
28
38
48 Liquid Temperature (TL)
19
29
39
49 Outdoor Temperature (TOA)
1A 2A 3A 4A PMV1 + 2
1B 2B 3B
-
PMV4
1C 2C 3C 4C Current of compressor 1 (I1)
1D 2D 3D 4D Current of compressor 2 (I2)
1E 2E 3E
-
Current of compressor 3 (I3)
1F
2F
3F
4F Outdoor fan current (IFan)
CODE No.
U1 U2 U3 U4
50
60
70
80 Rotation of compressor 1
51
61
71
81 Rotation of compressor 2
52
62
72
-
Rotation of compressor 3
53
63
73
83 Outdoor fan mode
54
64
74
84 Heat sink temperature of compressor IPDU1
55
65
75
85 Heat sink temperature of compressor IPDU2
56
66
76
-
Heat sink temperature of compressor IPDU3
57
67
77
87 Heat sink temperature of outdoor fan IPDU
58
-
-
-
In heat / cool collecting control (*4)
59
-
-
-
Pressure release (*4)
5A
-
-
-
Discharge temperature release (*4)
5B
-
-
-
Terminal unit release (U2 / U3 / U4 outdoor unit) (*4)
5F
6F
7F
8F Horse power of outdoor unit
*2 The upper digit of CODE No. indicates the outdoor unit No.
*3 [(The upper digit of CODE No.) – 4] indicates the outdoor unit No.
1✽, 5✽ ... U1 outdoor unit (Center unit)
2✽, 6✽ ... U2 outdoor unit (terminal unit 1)
3✽, 7✽ ... U3 outdoor unit (terminal unit 2)
4✽, 8✽ ... U4 outdoor unit (terminal unit 3)
*4 Only CODE No. 5* of U1 outdoor unit (Center unit) is displayed.
Data
Format
x 1 / 10
x 1 / 10
Data
Format
0 : Normal
1 : In collecting
0 : Normal
1 : In release
48
Remote controller display
Unit
example
x 100
MPa
[0123] = 1.23 MPa
x 100
MPa
x 1
°C
x 1
°C
x 1
°C
x 1
°C
[0024] = 24 °C
x 1
°C
x 1
°C
x 1
°C
x 1
°C
pls
[0050] = 500 pls
pls
x 10
A
x 10
A
[0135] = 13.5 A
x 10
A
x 10
A
Unit
Remote controller display example
x 10
rps
x 10
rps
[0642] = 64.2 rps
x 10
rps
x 1
Mode
[0058] = Mode 58
x 1
°C
x 1
°C
[0024] = 24 °C
x 1
°C
x 1
°C
[0010] = In heat collecting control
[0001] = In cool collecting control
control
[0010] = In pressure release control
[0001] = In discharge temperature release control
[0100] = In U2 outdoor unit release control
control
[0010] = In U3 outdoor unit release control
[0001] = In U4 outdoor unit release control
x 1
HP
[0016] = 16 HP

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents