Toshiba MD-VNK802HEXE Service Manual page 53

Table of Contents

Advertisement

9-2. How to check for errors
The remote controller (local remote controller or central control) is equipped with an LCD that displays the operation
status. If an error has occurred, see the following tables to check the error of the Air to Air Heat Exchanger with DX
Coil Unit using the failure diagnosis function.
The following tables show lists of the check codes indicated by each device. See the following tables for how to
check depending on the location.
• To check using the indoor remote controller or TCC-LINK central controller...See "Local remote controller &
TCC-LINK central controller" in the following table.
• To check from the outdoor unit...See "7-segment display of outdoor unit" in the following table.
Check code list (Indoor)
(Air to Air Heat Exchanger with DX Coil Unit)
Check code
Local remote
7-segment display of
controller &
outdoor unit
TCC-LINK
central
Sub code
controller
E03
E04
E08
E08 Duplicate indoor unit No. Duplicate indoor addresses
E10
E18
F01
F02
F03
F10
F11
F29
L02
L03
L07
L08
L08
L09
L20
L30
L30
Detected indoor unit No.
F17
F18
P01
P10
P10 Detected indoor unit No. Indoor overflow detected
P12
P31
Typical cause of error
Indoor unit - remote controller regular
communication error
Indoor unit - outdoor unit regular
communication error
Indoor MCU communication error
Header indoor unit - Follower indoor unit
regular communication error
Indoor heat exchange temperature sensor
(TCJ) error
Indoor heat exchange temperature sensor
(TC2) error
Indoor heat exchange temperature sensor
(TC1) error
Air temperature sensor (TSA) error
Discharge temperature sensor (TFA) error
Indoor unit or other P.C. board error
Outdoor unit model mismatch error
Duplicate indoor group header unit
settings
Group line in an individual indoor unit
Indoor group address not set
Indoor capacity not set
Duplicate central control addresses
External error input into indoor unit
(Interlock)
Outdoor air temperature sensor (TOA)
error
Return air temperature sensor (TRA) error
Indoor AC fan error
Indoor DC fan error
Other indoor unit errors
No data is received from the remote controller or network adapter.
(Also no central control communication)
No data is received from the outdoor unit.
The same address was detected.
There is a communication error between the main and motor micro
controller MCU.
Regular communication is not possible between the header and
follower indoor units.
Open-circuit or short-circuit of the heat exchange temperature
sensor (TCJ) was detected.
Open-circuit or short-circuit of the heat exchange temperature
sensor (TC2) was detected.
Open-circuit or short-circuit of the heat exchange temperature
sensor (TC1) was detected.
Open-circuit or short-circuit of the air temperature sensor (TSA)
was detected.
Open-circuit or short-circuit of the discharge temperature sensor
(TFA) was detected.
EEPROM error (Another error may have been detected)
The outdoor unit model is not supported.
There are multiple header units in the group.
There are one or more group-connected indoor units.
The indoor address group has not been set. (May also be detected
on the outdoor unit)
The indoor capacity has not been set.
Central control addresses are duplicate.
Stopped abnormally due to external error (CN80) input.
Open-circuit or short-circuit of the outdoor air temperature sensor
(TOA) was detected.
Open-circuit or short-circuit of the return air temperature sensor
(TRA) was detected.
The indoor AC fan error was detected. (Fan motor thermal relay)
The float switch has worked.
The indoor DC fan error (overcurrent, lock, etc.) was detected
The group follower unit cannot run due to E03 / L03 / L07 / L08
error of the header unit.
51