Connection Diagram - Toshiba MD-VNK802HEXE Service Manual

Table of Contents

Advertisement

Connection diagram

Connector
Connector
(White)
(Black)
Yellow
Yellow
Yellow
Yellow
Connector
Connector
(White *6)
(Red *6)
Yellow
Yellow
Red
Red
White
Red
Air to Air Heat
F02
Exchanger with
T15A
DX Coil Unit
250V~
Power supply for
Earth
indoor unit
220-240 V~, 50 Hz
220 V~, 60 Hz
represents the connector to switch
between Extra High and High.
Code
Parts name
CN***
Connector
F01
Fuse (Printed circuit board)
F02
Fuse (Motor)
FM1
Air supplying motor
FM2
Air exhausting motor
DAM
Damper motor
TRA
TRA sensor
TOA
TOA sensor
TSA
TSA sensor
1. The dotted line represents a wire procured locally, and the dashed line represents an option sold separately.
2.
represents a terminal block,
printed circuit board and
3.
represents a protective earth.
4.
represents a printed circuit board.
5. Using a no voltage a-contact input of the external input (sold separately), the following operations are available:
Between 1 and 2: Selecting the remote controller operation (Invalid / Valid)
Between 1 and 3: Adjusting the fan speed (Low / High)
Between 1 and 5: Operation (ON/OFF)
Use a microcurrent contact (DC12 V, 1 mA). In addition, ON/OFF operation is possible when using a voltage of
DC12 V or 24 V.
6. Orange wire (High) is connected as factory default. To switch to "Extra High", connect black wire's connector
instead of orange.
7. The unit cannot run when the temperature of the outdoor air is below -15 °C.
Red
Red
Black
(Red)
(White)
(White)
F01
T3.15A
250V~
Power
supply
(Black)
Yellow
Yellow
(VNK type only)
Code
TFA
TCJ, TC1, TC2 Indoor coil sensor
TB1
TB2
TB3
*1
TB4
*1
TB5
FS1
*1
MV1
represents a connection terminal,
represents a short circuit connector.
External output
*5 External input (sold separately)
(220-240V~, under 1A each)
No voltage a-contact input
Operation output
Common
External damper output
Abnormal / Bypass
mode output
(Red)
(Blue)
Gray
Gray
Purple
Pink
Blue
Blue
Pink
Pink
Parts name
TFA sensor
Terminal block (power source)
Terminal block (communication)
Terminal block (external output)
Terminal block (Humidistat)
Terminal block (Magnetic valve)
Float switch
Magnetic Valve
156
Installation Manual
1 Common
2 Remote controller operation
3 Fan speed
5 Operation
Voltage DC (12V, 24V)
input
(Blue)
(Yellow)
(Black)
(Brown)
(Black)
Indoor control
(Red)
circuit board
MCC1615
(Green)
(Yellow)
(Blue)
(White)
(Red)
(Red)
(Blue)
Wiring between indoor
and outdoor unit
Wired remote controller
(sold separately)
Code
Parts name
*1
DMV1
Decompression magnetic valve
PMV
Pluse modulating valve
SW701
DIP switch
43F11, 43F12
Relay for air supplying motor
43F21, 43F22
Relay for air exhausting motor
RY701, RY702 Relay for air supplying motor
RY704, RY705 Relay for exhausting motor
*
1: VNK type only
represents a connector on the
(Blue)
Wiring for
the remote
controller

Hide quick links: