Mitsubishi Electric F700 Instruction Manual page 46

Hide thumbs Also See for F700:
Table of Contents

Advertisement

9.
Acceleration → constant speed
Perform 20mA input.
The frequency value on the indication increases
according to Pr. 7 Acceleration time
until "
10.
Deceleration
Perform 4mA input.
The frequency value on the indication
decreases according to Pr. 8 Deceleration time
until "
" (0.00Hz) is displayed and the
operation status indication of FWD or REV
flickers.
The motor stops.
11.
Stop
Press
.
FWD or REV of the operation status indication
turns off.
REMARKS
Pr. 184 AU terminal function selection must be set to "4" (AU signal) (initial value). (Refer to
Change the frequency (50Hz) at the maximum current input (at 20mA, initial value)
Adjust the frequency in Pr. 126 Terminal 4 frequency setting gain frequency. (Refer to page 49.)
Change the frequency (0Hz) at the minimum current input (at 4mA, initial value)
Adjust the frequency in calibration parameter C5 Terminal 4 frequency setting bias frequency. (Refer to
Instruction Manual (applied).)
Operation
" (50.00Hz) is displayed.
Start/stop from the operation panel (PU
Display
Output of the
adjustment meter
(4 to 20mADC)
Output of the
adjustment meter
(4 to 20mADC)
Instruction Manual (applied).)
operation mode)
Flickering
Stop
41