7.
Mode/monitor check
Press
monitor/frequency monitor.
8.
Turn on the high speed switch (RH).
9.
Turn the start switch (STF or STR) on.
"
• 30Hz appears when RM is on and 10Hz
appears when RL is on.
10.
Stop
Turn the start switch (STF or STR) off.
The motor stops according to Pr. 8
Deceleration time.
[EXT] is not lit even when
Switchover of the operation mode with
50Hz, 30Hz and 10Hz are not output from RH, RM and RL respectively when they are turned on. ... Why?
Check for the setting of Pr. 4, Pr. 5, and Pr. 6 once again.
Check for the setting of Pr. 1 Maximum frequency and Pr. 2 Minimum frequency once again. (Refer to
page 52)
Check for the Pr. 79 setting once again. (Pr. 79 must be set to "0" or "2".) (Refer to page 57)
Check that Pr. 180 RL terminal function selection = "0", Pr. 181 RM terminal function selection = "1",
Pr. 182 RH terminal function selection = "2" and Pr. 59 Remote function selection = "0". (all are initial
values)
[FWD (or REV)] is not lit. ... Why?
Check that wiring is correct. Check it again.
Check that "60" is set in Pr. 178 STF terminal function selection (or "61" is set in Pr. 179 STR terminal
function selection)?
(all are initial values)
How is the frequency setting from 4 to 7 speed ?
The setting differs according to Pr. 24 to Pr. 27 (multi-speed setting). Refer to
(applied).
Perform multi-speed operation higher than 8 speed. ... How?
Use the REX signal to perform the operation. Refer to
REMARKS
· External operation is fixed by setting "2" (external operation mode) in Pr. 79 Operation mode selection when you do not want to take
time pressing
or when you want to use the current start command and frequency command. (Refer to page 57)
Operation
twice to choose the
" (40Hz) appears.
is pressed ... Why?
Make a start and stop with terminals
Display
High speed
Middle speed
ON
Low speed
Forward rotation
Reverse rotation
ON
Forward
rotation Reverse
rotation
OFF
is valid when Pr. 79 = "0" (initial value).
Instruction Manual (applied).
(external operation)
Stop
Instruction Manual
3
45