• FR-F740-00310 or more
1) Remove the upper screws.
2) Remove the lower screws.
3) Pull the jumper toward you to
remove.
4) Connect the separate power supply
cable for the control circuit to the
upper terminals (R1/L11, S1/L21).
Never connect the power cable to
the terminals in the lower stand.
Doing so will damage the inverter.
CAUTION
· Do not turn off the control power (terminals R1/L11 and S1/L21) with the main circuit power (R/L1, S/L2, T/L3) on. Doing so may
damage the inverter.
· Be sure to use the inverter with the jumpers across terminals R/L1-R1/L11 and S/L2-S1/L21 removed when supplying power from
other sources. The inverter may be damaged if you do not remove the jumper.
· The voltage should be the same as that of the main control circuit when the control circuit power is supplied from other than the
primary side of the MC.
· The power capacity should be 60VA or more for 00380 or less, 80VA or more for 00470 or more when separate power is supplied
from R1/L11, S1/L21.
· When the power supply used with the control circuit is different from the one used with the main circuit, make up a circuit which will
switch off the main circuit power supply terminals R/L1, S/L2, T/L3 when the control circuit power supply terminals R1/L11, S1/L21
are switched off.
· If the main circuit power is switched off (for 0.1s or more) then on again, the inverter resets and an alarm output will not be held.
R1/
S1/
L11
L21 Power supply
terminal block
for the control circuit
R/L1S/L2 T/L3
MC
Main power supply
00310, 00380
Power supply
terminal block for
the control circuit
3)
Power supply terminal block
for the control circuit
1)
2)
4)
00470, 00620
00770 or more
Wiring
R1/L11
S1/L21
U
V
W
2