2.3 Installation of the inverter and instructions
• Installation of the Inverter
Installation on the enclosure
00620 or less
• Install the inverter under the following conditions.
Ambient temperature and humidity
Measurement
position
Inverter
5cm
5cm
5cm
Measurement
position
Temperature: -10°C to 50°C (LD)
-10°C to 40°C (SLD*)
* Initial setting
Humidity: 90% RH maximum
Leave enough clearances and take
cooling measures.
REMARKS
For replacing the cooling fan of the 04320 or more, 30cm of space is necessary in front of the inverter.
Refer to page 112 for fan replacement.
• The inverter consists of precision mechanical and electronic parts. Never install or handle it in any of the following
conditions as doing so could cause an operation fault or failure.
Vertical mounting
(When installing two or
more inverters, install
them in parallel.)
6
00770 or more
Fix six positions for the FR-F740-
04320 to 08660 and fix eight positions
for the FR-F740-09620 to 12120.
01160 or less
10cm or more
5cm
5cm
or more *
or more *
10cm or more
*1cm or more for 00083 or less
2
Vibration(5.9m/s
2
* 2.9m/s
or more for the
Direct sunlight
04320 or more
Transportation by
holding the front cover
CAUTION
⋅ When encasing multiple inverters, install them in
parallel as a cooling measure.
⋅ Install the inverter vertically.
(front)
Clearances
01800 or more
20cm or more
10cm
10cm
or more
or more
20cm or more
or more*)
High temperature,
high humidity
Oil mist, flammable
gas, corrosive gas,
fluff, dust, etc.
Clearances (side)
Inverter
5cm
or more
Horizontal placement
Mounting to
combustible material
Vertical

Hide quick links: