Outdoor Units - Mitsubishi Electric FDT125VNVF Technical Manual

Table of Contents

Advertisement

(2) Outdoor units

Model
Item
Power source
Operation data
Nominal capacity
kW
Sound Pressure Level
dB(A)
Exterior dimensions
mm
Height x Width x Depth
Exterior appearance
(Munsell color)
Net weight
kg
Refrigerant equipment
Compressor type & Q'ty
Starting method
Refrigerant oil
Heat exchanger
Refrigerant control
Air handling equipment
Fan type & Q'ty
Motor <Starting method>
Air flow (Standard)
CMM
External static pressure
Pa
Shock & vibration absorber
Electric heater
Safety equipment
Installation data
mm
Refrigerant piping size
Connecting method
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Refrigerant Quantity
Drain
Insulation for piping
IP code
Standard Accessories
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
Cooling
Heating
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber.
During operation these value are somewhat higher due to ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 230V50Hz or 220V60Hz.
Cooling
10.0 [ 4.0 (Min.)~11.2 (Max.)]
W
W
Max.30m (Outdoor unit is higher)
Max.15m (Outdoor unit is lower)
R410A 3.8kg in outdoor unit (incl. the amount for the piping of : 30m)
Outdoor air temperature
DB
WB
DB
27˚C
19˚C
35˚C
20˚C
7˚C
FDC100VN
220-240V~50Hz / 220V~60Hz
49
845×970×370
Stucco White
(4.2Y7.5/1.1) near equivalent
81
RMT5126MDE2 × 1
Direct line start
0.9 M-MA68
Straight fin & inner grooved tubing
Electronic expansion valve
Propeller fan × 1
86 < Direct line start >
Cooling : 75, Heating : 73
0
Rubber sleeve (for Compressor )
20 (Crank case heater)
Internal thermostat for fan motor
Abnormal discharge temperature protection.
Liquid line :φ9.52 (3/8")
Gas line
:φ15.88 (5/8")
Flare piping
Max.50m
Holes sizeφ20 x 3pcs
Necessary (both Liquid & Gas lines)
IP24
Edging
WB
24˚C
6˚C
465
-
-
'12 • PAC-T-174
Adapted to RoHS directive
Heating
11.2 [ 4.0 (Min.)~12.5 (Max.)]
See page 154
PJF000Z294

Hide quick links:

Advertisement

Table of Contents
loading