Mitsubishi Electric FDT125VNVF Technical Manual page 171

Table of Contents

Advertisement

(3) Ceiling susponded type (FDEN)
(a) Single type
FDEN100VNVF
Model
Indoor unit
Cool Mode
Outdoor
18 DB
21 DB
air temp.
12 WB
14 WB
DB
TC
SHC
TC
SHC
11
13
15
17
19
21
23
25
8.93 7.63 9.64 7.50 10.31 8.09 10.62 8.03 10.95 7.97 11.61 8.38 12.27 8.23
27
8.86 7.59 9.64 7.50 10.34 8.10 10.65 8.04 10.96 7.98 11.57 8.37
29
8.80 7.57 9.50 7.44 10.17 8.03 10.49 7.98 10.81 7.92 11.45 8.33
31
8.73 7.53 9.35 7.38 9.99 7.96 10.32 7.91 10.66 7.87 11.32 8.28
33
8.22 7.04
8.58 7.47 9.21 7.32 9.82 7.89 10.16 7.85 10.51 7.81 11.19 8.24
35
8.05 6.96
8.44 7.40 9.06 7.25 9.64 7.82 10.00 7.79 10.36 7.76 11.07 8.20
37
7.92 6.90
8.30 7.34 8.91 7.19 9.46 7.75 9.79 7.71 10.13 7.67 10.80 8.11
39
7.78 6.83
8.16 7.28 8.75 7.12 9.28 7.68 9.59 7.64
41
7.64 6.76
8.02 7.21 8.60 7.06 9.09 7.61 9.38 7.56
43
7.50 6.69
7.88 7.15 8.45 7.00 8.91 7.54 9.18 7.49
FDEN100VSVF
Model
Indoor unit
Cool Mode
Outdoor
18 DB
21 DB
air temp.
12 WB
14 WB
DB
TC
SHC
TC
SHC
11
13
15
17
19
21
23
25
8.93 7.63 9.64 7.50 10.31 8.09 10.62 8.03 10.95 7.97 11.61 8.38 12.27 8.23
27
8.86 7.59 9.64 7.50 10.34 8.10 10.65 8.04 10.96 7.98 11.57 8.37
29
8.80 7.57 9.50 7.44 10.17 8.03 10.49 7.98 10.81 7.92 11.45 8.33
31
8.73 7.53 9.35 7.38
33
8.22 7.04
8.58 7.47 9.21 7.32
35
8.05 6.96
8.44 7.40 9.06 7.25
37
7.92 6.90
8.30 7.34 8.91 7.19
39
7.78 6.83
8.16 7.28 8.75 7.12
41
7.64 6.76
8.02 7.21 8.60 7.06
43
7.50 6.69
7.88 7.15 8.45 7.00
Note(1) These data show average statuses.
Note(1)
Depending on the system control, there may be ranges where the operation is not conducted continuously.
Note(1)
These data show the case where the operation frequency of a compressor is fixed.
(2) Capacities are based on the following conditions.
(2)
Corresponding refrigerant piping length :7.5m
(2)
Level difference of Zero.
(3) Symbols are as follows.
TC : Total cooling capacity
SHC : Sensible heat capacity
FDEN100VF
Outdoor unit
Indoor air temperature
23 DB
26 DB
27 DB
16 WB
18 WB
19 WB
TC
SHC
TC
SHC
TC
SHC
8.12 6.86 8.59 7.42 8.82 7.35
8.50 7.02 9.00 7.57 9.26 7.52
8.88 7.18 9.42 7.74 9.69 7.68
9.26 7.34 9.84 7.90 10.12 7.84 10.43 7.78 11.05 8.19 11.67 8.04
9.46 7.42 10.05 7.98 10.34 7.92 10.65 7.86 11.29 8.27 11.92 8.12
9.65 7.51 10.25 8.06 10.56 8.01 10.88 7.95 11.52 8.35 12.16 8.19
9.65 7.51 10.28 8.08 10.59 8.02 10.91 7.96 11.56 8.37 12.21 8.21
FDEN100VF
Outdoor unit
Indoor air temperature
23 DB
26 DB
27 DB
16 WB
18 WB
19 WB
TC
SHC
TC
SHC
TC
SHC
8.12 6.86
8.59 7.42 8.82 7.35 9.07 7.30
8.50 7.02
9.00 7.57 9.26 7.52 9.52 7.45 10.06 7.87 10.60 7.72
8.88 7.18
9.42 7.74 9.69 7.68 9.98 7.62 10.56 8.03 11.14 7.88
9.26 7.34
9.84 7.90 10.12 7.84 10.43 7.78 11.05 8.19 11.67 8.04
9.46 7.42 10.05 7.98 10.34 7.92 10.65 7.86 11.29 8.27 11.92 8.12
9.65 7.51 10.25 8.06 10.56 8.01 10.88 7.95 11.52 8.35 12.16 8.19
9.65 7.51 10.28 8.08 10.59 8.02 10.91 7.96 11.56 8.37 12.21 8.21
9.99 7.96 10.32 7.91 10.66 7.87 11.32 8.28
9.82 7.89 10.16 7.85 10.51 7.81 11.19 8.24
9.64 7.82 10.00 7.79 10.36 7.76 11.07 8.20
9.46 7.75 9.79 7.71 10.13 7.67 10.80 8.11
9.28 7.68 9.59 7.64 9.90 7.59 10.53 8.02
9.09 7.61 9.38 7.56 9.68 7.51 10.26 7.93
8.91 7.54 9.18 7.49 9.45 7.43
FDC100VN
(kW)
28 DB
31 DB
33 DB
20 WB
22 WB
24 WB
TC
SHC
TC
SHC
TC
SHC
9.07 7.30 9.56 7.71 10.06 7.56
9.52 7.45 10.06 7.87 10.60 7.72
9.98 7.62 10.56 8.03 11.14 7.88
9.90 7.59 10.53 8.02
9.68 7.51 10.26 7.93
9.45 7.43 9.99 7.84
FDC100VS
(kW)
28 DB
31 DB
33 DB
20 WB
22 WB
24 WB
TC
SHC
TC
SHC
TC
SHC
9.56 7.71 10.06 7.56
9.99 7.84
170
-
-
'12 • PAC-T-174
Heat Mode
Outdoor
Indoor air temperature
air temp.
DB
DB
WB
16
18
20
-19.8 -20
5.64 5.62 5.60 5.58 5.56
-17.7 -18
5.97 5.95 5.92 5.90 5.87
-15.7 -16
6.30 6.27 6.25 6.22 6.19
-13.5 -14
6.66 6.63 6.60 6.57 6.54
-11.5 -12
7.03 6.99 6.96 6.93 6.90
-9.5
-10
7.39 7.36 7.32 7.29 7.25
-7.5
-8
7.75 7.72 7.68 7.64 7.60
-5.5
-6
7.92 7.88 7.85 7.80 7.76
-3.0
-4
8.10 8.05 8.01 7.97 7.92
-1.0
-2
8.27 8.22 8.18 8.13 8.08
1.0
0
8.44 8.39 8.34 8.29 8.24
2.0
1
8.52 8.47 8.42 8.37 8.32
3.0
2
9.08 9.03 8.98 8.94 8.90
5.0
4
10.21 10.15 10.09 10.08 10.07
7.0
6
11.33 11.27 11.20 11.22 11.23
9.0
8
11.78 11.71 11.64 11.62 11.59
11.5
10
12.23 12.16 12.09 12.02 11.94
13.5
12
12.91 12.83 12.75 12.65 12.60
15.5
14
13.59 13.50 13.42 13.29 13.26
16.5
16
13.93 13.84 13.75 13.61 13.59
PFA003Z924
Heat Mode
Outdoor
Indoor air temperature
air temp.
DB
DB
WB
16
18
20
-19.8 -20
5.64 5.62 5.60 5.58 5.56
-17.7 -18
5.97 5.95 5.92 5.90 5.87
-15.7 -16
6.30 6.27 6.25 6.22 6.19
-13.5 -14
6.66 6.63 6.60 6.57 6.54
-11.5 -12
7.03 6.99 6.96 6.93 6.90
-9.5
-10
7.39 7.36 7.32 7.29 7.25
-7.5
-8
7.75 7.72 7.68 7.64 7.60
-5.5
-6
7.92 7.88 7.85 7.80 7.76
-3.0
-4
8.10 8.05 8.01 7.97 7.92
-1.0
-2
8.27 8.22 8.18 8.13 8.08
1.0
0
8.44 8.39 8.34 8.29 8.24
2.0
1
8.52 8.47 8.42 8.37 8.32
3.0
2
9.08 9.03 8.98 8.94 8.90
5.0
4
10.21 10.15 10.09 10.08 10.07
7.0
6
11.33 11.27 11.20 11.22 11.23
9.0
8
11.78 11.71 11.64 11.62 11.59
11.5
10
12.23 12.16 12.09 12.02 11.94
13.5
12
12.91 12.83 12.75 12.65 12.60
15.5
14
13.59 13.50 13.42 13.29 13.26
16.5
16
13.93 13.84 13.75 13.61 13.59
PFA003Z924
(kW)
22
24
A
(kW)
22
24
A

Hide quick links: