(b) In case of RC-EX1A remote controller
[Operating procedure]
➀ On the TOP screen, touch the buttons in the order of "Menu" ➝ "Next" ➝ "Service & Maintenance" ➝ "Service password" ➝
"Set" ➝ "Error display" ➝ "Error history".
➁ When only one indoor unit is connected to the remote controller, followings will be displayed.
1. When there is any anomaly: "Loading. Wait a while" is displayed, followed by the operation data at the occurrence of anomaly.
Contents of display
・ Error code
・ Number and data item
2. When there is no anomaly: "No anomaly" is displayed, and this mode is terminated.
➂ When two or more indoor units are connected to the remote controller, followings will be displayed.
1. When there is any anomaly: If the unit having anomaly is selected on the "Select IU" screen, "Loading. Wait a while" is
displayed, followed by the operation data at the occurrence of anomaly.
Contents of display
・ Indoor unit No.
・ Error code
・ Number and data item
2. When there is no anomaly: "No anomaly" is displayed, ant this mode is terminated.
Note (1) When the number of connected units cannot be shown in a page, select "Next".
➃ If you press [RUN/STOP] button, the display returns to the TOP screen.
◎ If you touch "Back" button on the way of setting, the display returns to the last precious screen.
Note (1) When two remote controllers are used to control indoor units, the check of anomaly operation data can be made on the
master remote controller only. (It cannot be operated from the slave remote controller.)
■ Anomaly operation data (Corresponding data may not be provided depending on models. Such items will not be displayed.)
Number
Data Item
(Operation Mode)
01
(Set Temperature)
02
(Return Air Temperature)
03
04
(Remote Controller Thermistor Tempeature)
05
(Indoor Heat Exchanger Thermistor / U Bend)
06
(Indoor Heat Exchanger Thermistor /Capillary)
07
(Indoor Heat Exchanger Thermistor /Gas Header)
08
(Indoor Unit Fan Speed)
(Frequency Requirements)
09
10
(Response Frequency)
(Pulse of Indoor Unit Expansion Value)
11
(Total Running Hours of The Indoor Unit)
12
21
(Outdoor Air Temperature)
(Outdoor Heat Exchanger Thermistor)
22
23
(Outdoor Heat Exchanger Thermistor)
(Compressor Frequency)
24
25
(High Pressure)
Contents of display
26
(Low Pressure)
P.322
27
(Discharge Pipe Temperature)
P.322
(Comp Bottom Temperature)
28
P.323
(Current)
29
P.322
(Target Super Heat)
30
P.322
(Super Heat)
31
P.323
P.323
(Discharge Pipe Super Heat)
32
P.324
33
(Protection State No. of The Compressor)
P.323
34
(Outdoor Unit Fan Speed)
P.324
35
(63H1 On/Off)
P.324
36
(Defrost Control On/Off)
P.323
37
(Total Running Hours of The Compressor)
P.324
38
(Pulse of The Outdoor Unit Expansion Valve EEVC)
P.323
39
(Pulse of The Outdoor Unit Expansion Valve EEVH)
P.325
No.
"0"
"1"
"2"
"3"
"4"
"5"
"6"
"7"
"8"
"9"
"10" Power transistor protection control
"11" Power transistor anomaly (Overheat)
"12" Compression ratio control
"13" Spare
"14" Dewing prevention control
"15" Current safe control of inverter secondary current
"16" Stop by compressor rotor lock
"17" Stop by compressor startup failure
In case of FDC71-140 refer to
Note(1) Operation data display on the remote controller.
.(a).1)
Note(2) Common item.
.(a).2)
.(g)
.(b).1) (c).1)
.(b).2)
.(e).1)
.(e).2)
.(k)
.(g)
.(h)
.(i)
.(f)
.(l)
.(g)
.(p)
Details of Compressor protection status No. 33
Contents of display
Normal
Discharge pipe temperature protection control
Discharge pipe temperature anomaly
Current safe control of inverter primary current
High pressure protection control
High pressure anomaly
Low pressure protection control
Low pressure anomaly
Anti-frost prevention control
Current cut
Data is dispalyed until canceling the protection control.
In case of multiple protections controlled, only the younger No. is displayed.
In heating mode.
During protection control by the command signal for reducing compressor
frequency from indoor unit, No. "4" is displayed.
In cooling and dehumidifying mode.
During protection control by the command signal for reducing compressor
frequency from indoor unit, No. "8" is displayed.
351
-
-
'12 • PAC-T-174
In case of FDC71-140 refer to
Note(1) Operation data display on the
P.322
.(a).1)
Note(2) Common item.
P.322
.(a).2)
P.323
.(g)
P.322
.(b).1) (c).1)
P.322
.(b).2)
P.323
.(e).1)
P.323
.(e).2)
P.324
.(k)
P.323
.(g)
P.324
.(h)
P.324
.(i)
P.323
.(f)
P.324
.(l)
P.323
.(g)
P.325
.(p)
Data is dispalyed until cancel
In case of multiple protection
In heating mode.
During protection control by
frequency from indoor unit,
In cooling and dehumidifyin
During protection control by
frequency from indoor unit,