Mitsubishi Electric FDT125VNVF Technical Manual page 127

Table of Contents

Advertisement

POWER SOURCE 3∼380ー415V 50Hz/380V 60Hz
TB
F(10A)
RD
L1
RD
WH
L2
BL
L3
BK
N
BK
GN
L1i
L2i
L3i
Ni
NOISE FILTER
GN
PWB3
E
L1o
L2o
L3o
No
BK
CT
CNW
(BK)
52X
u
RD
R5
AC1
AC2
AC3
CNW1
CNO1
CNA1
(WH)
BL
+4
(RD)
DM
(WH)
BL
DC FAN
RD
-6
CNO2
CNA2
PWB4
BL
(RD)
(WH)
L
CNI3
CNI1
INVERTER
P2
(WH)
(WH)
PWB2
P3
I P M
N2
P
N
U V W
+
V W
U
MS
+
3∼
CM
Power cable, indoor-outdoor connecting wires
MAX over current
Model
Power cable size
Power cable length
2
(A)
(mm)
200
19
3.5
250
22
5.5
※At the connection with the duct type indoor unit.
MAX over current
Power cable size
Power cable length
Model
2
(A)
(mm)
200
24
5.5
250
27
The specifications shown in the above table are for units without heaters. For units with heaters, refer
to the installation instructions or the construction instructions of the indoor unit.
Switchgear of Circuit breaker capacity which is calculated from MAX. over current should be chosen
along the regulations in each country.
The cable specifications are based on the assumption that a metal or plastic conduit is used with no
more than three cables contained in a conduit and a voltage drop is 2%. For an installation falling
outside of these conditions, please follow the internal cabling regulations. Adapt it to the regulation
in effect in each country.
TB
RD
TO INDOOR UNIT
1
BK
2
[
]
POWER WIRES
1
2
3
3
SIGNAL WIRE
SM1
SM2
M
M
6
5
4 3
2
1
6
5
4
3
2
1
CNW2
CNEEV1
CNEEV2
(OR)
(WH)
(RD)
CONTROL
PWB1
ON
52X1
52X3
52X6
OFF
1
2
3
LED1
LED2
SW3
CNR
CNS
CNM
CNH
CNU
CNB
(WH)
(RD)
(GR)
(BR)
(BL)
(RD)
CH
20S
52X
63H1
THo-H
THo-R2
THo-R1
THo-D
indoor-outdoor
Earth wire size
wire size x number
(m)
(mm)
21
φ1.6mm x 3
φ1.6
31
indoor-outdoor
Earth wire size
wire size x number
(m)
(mm)
29
φ1.6mm x 3
φ1.6
26
FMO1
FMO2
M
M
7
6
5 4 1
7
6
5 4 1
CNFAN1
CNFAN2
(WH)
(WH)
ON
Mark
Color
OFF
4
1 2
3
4
BK
Black
SW1
SW5
BL
Blue
BR
Brown
CNTH
CNPS
CNIP
(WH)
(Y)
(WH)
GR
Gray
P
Pink
OR
Orange
LPT
RD
Red
THo-S
THo-A
THo-IPM
WH
White
Y
Yellow
Y/GN
Yellow/Green
Local setting switch SW3(Set up at shipment OFF)
The defrosting operation interval becomes shorter
by turning ON this switch. This switch should be
Defrost control change
SW3-1
turned ON in the area where outside temperature
becomes below the freezing point.
When this switch is turned ON, the outdoor unit
fan will run for 30 seconds in every 10 minutes,
when outdoor temperature falls to 3 or lower and
SW3-2
Snow guard fan control
the compressor is not runnning when the unit is used
in a very snowy country, set this switch to ON.
Method of trial operation
1
Trial operation can be performed by using SW3-3,4.
2
Compressor will be in the operation when
SW3-3 is ON.
SW3-3,4
Trial operation
3
Cooling trial operation will be performed when
SW3-4 is OFF, and heating trial operation when
SW3-4 is ON.
4
Be sure to turn OFF SW3-3 after the trial operation
is finished.
Item
Description
CnA∼Z
Connector
CH
Crankcase heater
CM
Compressor motor
CT
Current sensor
DM
Diode module
F
Fuse
FM01,02
Fan motor
IPM
Intelligent power module
L
Reactor
LED1
Indication lamp(GREEN)
LED2
Indication lamp(RED)
LPT
Low pressure sensor
SM1
Expansion valve for cooling
SM2
Expansion valve for heating
SW1
Pump down switch
SW3,5
Local setting switch
TB
Terminal block
Thermistor(Outdoor air temp.)
THo-A
Thermistor(Discharge pipe temp.)
THo-D
Thermistor (Camp.undeneth temp.)
THo-H
THo-IPM
Thermistor(IPM)
THo-R1,2
Thermistor(Heat exchanger pipe temp. )
THo-S
Thermistor(Suction pipe temp.)
20S
Solenoid valve for 4 way valve
52X1
Auxilliary relay(for CH)
52X3
Auxilliary relay(for 20S)
52X6
Auxilliary relay(for 52X)
63H1
High pressure switch

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents