Mitsubishi Electric FDT125VNVF Technical Manual page 172

Table of Contents

Advertisement

FDEN125VNVF
Model
Indoor unit
Cool Mode
Outdoor
18 DB
21 DB
air temp.
12 WB
14 WB
DB
TC
SHC
TC
SHC
11
13
15
17
19
21
23
25
11.16 8.63 12.06 8.41 12.89 9.00 13.27 8.88 13.68 8.77 14.51 9.14 15.34 8.86
27
11.08 8.59 12.05 8.41 12.92 9.01 13.31 8.90 13.69 8.77 14.47 9.13
29
11.00 8.56 11.87 8.34 12.71 8.93 13.11 8.83 13.51 8.71 14.31 9.08
31
10.92 8.52 11.69 8.26 12.49 8.85 12.90 8.75 13.32 8.65 14.15 9.03
33
10.27 8.02 10.72 8.43 11.51 8.19 12.27 8.77 12.70 8.68 13.13 8.59 13.99 8.98
35
10.07 7.92 10.55 8.36 11.33 8.12 12.06 8.69 12.50 8.61 12.94 8.52 13.83 8.94
37
9.90 7.84 10.38 8.29 11.13 8.04 11.83 8.61 12.24 8.53 12.66 8.43 13.50 8.84
39
9.72 7.76 10.20 8.21 10.94 7.97 11.60 8.53 11.99 8.44 12.38 8.34 13.16 8.74
41
9.55 7.68 10.02 8.13 10.75 7.89 11.37 8.45 11.73 8.35 12.09 8.25 12.82 8.64
43
9.38 7.60 9.85 8.06 10.56 7.82 11.14 8.37 11.47 8.27 11.81 8.16 12.48 8.55
Model
FDEN125VSVF
Indoor unit
Cool Mode
Outdoor
18 DB
21 DB
air temp.
12 WB
14 WB
DB
TC
SHC
TC
SHC
11
13
15
17
19
21
23
25
11.16 8.63 12.06 8.41 12.89 9.00 13.27 8.88 13.68 8.77 14.51 9.14 15.34 8.86
27
11.08 8.59 12.05 8.41 12.92 9.01 13.31 8.90 13.69 8.77 14.47 9.13
29
11.00 8.56 11.87 8.34 12.71 8.93 13.11 8.83 13.51 8.71 14.31 9.08
31
10.92 8.52 11.69 8.26 12.49 8.85 12.90 8.75 13.32 8.65 14.15 9.03
33
10.27 8.02 10.72 8.43 11.51 8.19 12.27 8.77 12.70 8.68 13.13 8.59 13.99 8.98
35
10.07 7.92 10.55 8.36 11.33 8.12 12.06 8.69 12.50 8.61 12.94 8.52 13.83 8.94
37
9.90 7.84 10.38 8.29 11.13 8.04 11.83 8.61 12.24 8.53 12.66 8.43 13.50 8.84
39
9.72 7.76 10.20 8.21 10.94 7.97 11.60 8.53 11.99 8.44 12.38 8.34 13.16 8.74
41
9.55 7.68 10.02 8.13 10.75 7.89 11.37 8.45 11.73 8.35 12.09 8.25 12.82 8.64
43
9.38 7.60 9.85 8.06 10.56 7.82 11.14 8.37 11.47 8.27 11.81 8.16 12.48 8.55
Note(1) These data show average statuses.
Note(1)
Depending on the system control, there may be ranges where the operation is not conducted continuously.
Note(1)
These data show the case where the operation frequency of a compressor is fixed.
(2) Capacities are based on the following conditions.
(2)
Corresponding refrigerant piping length :7.5m
(2)
Level difference of Zero.
(3) Symbols are as follows.
TC : Total cooling capacity
SHC : Sensible heat capacity
FDEN125VF
Outdoor unit
Indoor air temperature
23 DB
26 DB
27 DB
16 WB
18 WB
19 WB
TC
SHC
TC
SHC
TC
SHC
10.15 7.66 10.74 8.23 11.03 8.12 11.34 8.01 11.96 8.40 12.57 8.15
10.63 7.85 11.26 8.41 11.57 8.30 11.91 8.19 12.58 8.58 13.25 8.31
11.10 8.03 11.78 8.59 12.11 8.48 12.47 8.37 13.20 8.75 13.92 8.48
11.58 8.22 12.29 8.78 12.65 8.67 13.04 8.56 13.82 8.93 14.59 8.66
11.82 8.32 12.56 8.88 12.92 8.76 13.32 8.65 14.11 9.02 14.90 8.74
12.06 8.41 12.82 8.97 13.19 8.86 13.60 8.74 14.40 9.11 15.20 8.82
12.06 8.41 12.85 8.98 13.23 8.87 13.64 8.76 14.45 9.12 15.27 8.84
FDEN125VF
Outdoor unit
Indoor air temperature
23 DB
26 DB
27 DB
16 WB
18 WB
19 WB
TC
SHC
TC
SHC
TC
SHC
10.15 7.66 10.74 8.23 11.03 8.12 11.34 8.01 11.96 8.40 12.57 8.15
10.63 7.85 11.26 8.41 11.57 8.30 11.91 8.19 12.58 8.58 13.25 8.31
11.10 8.03 11.78 8.59 12.11 8.48 12.47 8.37 13.20 8.75 13.92 8.48
11.58 8.22 12.29 8.78 12.65 8.67 13.04 8.56 13.82 8.93 14.59 8.66
11.82 8.32 12.56 8.88 12.92 8.76 13.32 8.65 14.11 9.02 14.90 8.74
12.06 8.41 12.82 8.97 13.19 8.86 13.60 8.74 14.40 9.11 15.20 8.82
12.06 8.41 12.85 8.98 13.23 8.87 13.64 8.76 14.45 9.12 15.27 8.84
FDC125VN
(kW)
28 DB
31 DB
33 DB
20 WB
22 WB
24 WB
TC
SHC
TC
SHC
TC
SHC
FDC125VS
(kW)
28 DB
31 DB
33 DB
20 WB
22 WB
24 WB
TC
SHC
TC
SHC
TC
SHC
171
-
-
'12 • PAC-T-174
Heat Mode
Indoor air temperature
Outdoor
air temp.
DB
DB
WB
16
18
20
-19.8 -20
7.06 7.03 7.00 6.97 6.95
-17.7 -18
7.46 7.43 7.41 7.37 7.34
-15.7 -16
7.87 7.84 7.81 7.77 7.74
-13.5 -14
8.33 8.29 8.26 8.22 8.18
-11.5 -12
8.78 8.74 8.70 8.66 8.62
-9.5
-10
9.24 9.19 9.15 9.11 9.06
-7.5
-8
9.69 9.65 9.60 9.55 9.50
-5.5
-6
9.91 9.86 9.81 9.75 9.70
-3.0
-4
10.12 10.07 10.01 9.96 9.90
-1.0
-2
10.33 10.28 10.22 10.16 10.10
1.0
0
10.55 10.49 10.43 10.36 10.30
2.0
1
10.65 10.59 10.53 10.47 10.40
3.0
2
11.36 11.29 11.22 11.18 11.13
5.0
4
12.76 12.69 12.61 12.60 12.58
7.0
6
14.16 14.08 14.00 14.02 14.04
9.0
8
14.72 14.64 14.56 14.52 14.49
11.5
10
15.28 15.20 15.11 15.02 14.93
13.5
12
16.13 16.04 15.94 15.82 15.75
15.5
14
16.98 16.88 16.77 16.62 16.58
16.5
16
17.41 17.30 17.19 17.02 16.99
PFA003Z924
Heat Mode
Indoor air temperature
Outdoor
air temp.
DB
DB
WB
16
18
20
-19.8 -20
7.06 7.03 7.00 6.97 6.95
-17.7 -18
7.46 7.43 7.41 7.37 7.34
-15.7 -16
7.87 7.84 7.81 7.77 7.74
-13.5 -14
8.33 8.29 8.26 8.22 8.18
-11.5 -12
8.78 8.74 8.70 8.66 8.62
-9.5
-10
9.24 9.19 9.15 9.11 9.06
-7.5
-8
9.69 9.65 9.60 9.55 9.50
-5.5
-6
9.91 9.86 9.81 9.75 9.70
-3.0
-4
10.12 10.07 10.01 9.96 9.90
-1.0
-2
10.33 10.28 10.22 10.16 10.10
1.0
0
10.55 10.49 10.43 10.36 10.30
2.0
1
10.65 10.59 10.53 10.47 10.40
3.0
2
11.36 11.29 11.22 11.18 11.13
5.0
4
12.76 12.69 12.61 12.60 12.58
7.0
6
14.16 14.08 14.00 14.02 14.04
9.0
8
14.72 14.64 14.56 14.52 14.49
11.5
10
15.28 15.20 15.11 15.02 14.93
13.5
12
16.13 16.04 15.94 15.82 15.75
15.5
14
16.98 16.88 16.77 16.62 16.58
16.5
16
17.41 17.30 17.19 17.02 16.99
PFA003Z924
(kW)
22
24
A
(kW)
22
24
A

Hide quick links:

Advertisement