Mitsubishi Electric FDT125VNVF Technical Manual page 14

Table of Contents

Advertisement

Model
Item
Power source
Operation data
Nominal capacity
kW
Power consumption
kW
Running current
Power factor
%
Inrush current
Sound Pressure Level
dB(A)
Exterior dimensions
mm
Height × Width × Depth
Exterior appearance
(Munsell color)
Net weight
kg
Refrigerant equipment
Compressor type & Q'ty
Starting method
Refrigerant oil
Heat exchanger
Refrigerant control
Air handling equipment
Fan type & Q'ty
Motor <Starting method>
Air flow (Standard)
CMM
External static pressure
Pa
Outside air intake
Air filter, Q'ty
Shock & vibration absorber
Insulation (noise & heat)
Electric heater
Remote controller
Room temperature control
Safety equipment
Installation data
mm
Refrigerant piping size
Connecting method
Refrigerant line (one way) length
Vertical height difference between
outdoor unit and indoor unit
Refrigerant Quantity
Drain pump
Drain
Insulation for piping
IP code
Standard Accessories
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Operation
Cooling
27˚C
Heating
(2) This packaged air-conditioner is manufactured and tested in conformity with the ISO.
(3) Sound pressure level indicates the value in an anechoic chamber. During operation these value are somewhat higher due to
ambient temperature.
(4) The operation data indicates when the air-conditioner is operated at 400V50Hz or 380V60Hz.
(5) Indoor unit specifications for one unit. Capacity and operation data is two indoor units are combined and run together.
(6) Branching pipe set "DIS-WA1" × 1 (option). ① : Pipe of O/U~Branch, ② : Pipe of Branch~I/U
(7) When wireless remote controller is used, fan is 3 speed setting (Hi-Me-Lo) only.
Indoor unit FDT50VF (2 units)
Panel T-PSA-3BW-E
Cooling
10.0 [ 4.0 (Min.)~11.2 (Max.)]
2.94
A
4.3 / 4.6
99 / 97
A
P-Hi : 39 Hi : 33 Me : 31 Lo : 30
Unit 246 × 840 × 840
Panel 35 × 950 × 950
Plaster White
(6.8Y8.9/0.2) near equivalent
UNIT 22 PANEL 5.5
Louver fin & inner grooved tubing
Turbo fan × 1
W
50 < Direct line start >
P-Hi : 20 Hi : 18 Me : 16 Lo : 14
possible
Pocket plastic net × 1 (Washable)
Rubber sleeve (for fan motor)
Polyurethane form
W
wired : RC-EX1A , RC-E5 (option) wireless : RCN-T-36W-E (option)
Thermostat by electronics
Overload protection for fan motor
Frost protection thermostat
Liquid line : I/Uφ6.35 (1/4") ②φ9.52 (3/8") × 0.8 ①φ9.52 (3/8") × 0.8
: I/Uφ12.7 (1/2") ②φ12.7 (1/2") × 0.8 ①φ15.88 (5/8") × 1.0 O/Uφ15.88 (5/8")
Gas line
Flare piping
Max.30m (Outdoor unit is higher)
Max.15m (Outdoor unit is lower)
R410A 3.8kg (Pre-charged up to the piping length of 30m) Outdoor unit
Built-in Drain pump
Hose Connectable with VP25
IPXO
Mounting kit, Drain hose
Outdoor air temperature
DB
WB
DB
19˚C
35˚C
20˚C
7˚C
FDT100VSPVF
5 < Max.running current 15 >
0
Max.50m
Necessary (both Liquid & Gas lines)
WB
24˚C
6˚C
13
-
-
'12 • PAC-T-174
Adapted to RoHS directive
Outdoor unit FDC100VS
380-410V 3N~50Hz / 380V 3N~60Hz
Heating
11.2 [ 4.0 (Min.)~12.5 (Max.)]
3.09
4.5 / 4.8
99 / 98
49
845 × 970 × 370
Stucco White
(4.2Y7.5/1.1) near equivalent
83
RMT5126MDE3 × 1
Direct line start
0.9 M-MA68
Straight fin & inner grooved tubing
Electronic expansion valve
Propeller fan × 1
86 < Direct line start >
Cooling : 75 Heating : 73
0
Rubber sleeve (for Compressor)
20 (Crank case heater)
Internal thermostat for fan motor
Abnormal discharge temperature protection.
O/Uφ9.52 (3/8")
Flare piping
See page 154
Holes size φ20 × 3pcs
IPX4
Edging
PJF000Z294

Hide quick links:

Advertisement

Table of Contents
loading