Preset point of the protective devices
Parts name
Thermistor
(for protection over-
loading in heating)
Thermistor
(for frost prevention)
Thermistor
(for protection high
pressure in cooling.)
Thermistor
(for detecting dis-
charge pipe temp.)
High pressure switch
(for protection)
Low pressure sensor
(for protection)
Note (1) Values in ( ) are for the SRK models.
Equipped
Mark
100, 125, 140 model
unit
Th I -R
(TH1)
Indoor unit
Th I -R
(TH1)
Tho-R
Outdoor unit
Tho-D
Outdoor unit
Outdoor unit
63H1
Outdoor unit
LPT
200, 250 model
OFF 63˚C
OFF 16˚C
ON 56˚C
ON 17˚C
OFF 63˚C
OFF 8˚C
ON 56˚C
ON 2.5˚C
OFF 51˚C
ON 65˚C
OFF 115˚C
OFF 135˚C
ON 85˚C
OFF 4.15MPa
ON 3.15MPa
OFF 0.227MPa
ON 0.079MPa
151
-
-
'12 • PAC-T-174
ON 90˚C