Indoor display
Error code
E36
Remote controller:
inverter PCB
1. Applicable model
All models
2. Error detection method
For the error detection method,
refer to the protective control by
controlling compressor rotation
speed and cooling high pressure
protective control of micro
computer control function for
corresponding models.
3. Condition of Error displayed
When discharge pipe
temperature anomaly is detected
2 times within 60 minutes or
this anomalous state is detected
60 minutes continuously
including compressor stop.
4. Presumable cause
• Defective outdoor control
PCB
• Defective discharge pipe
temperature thermistor
• Clogged filter
• Indoor, outdoor unit
installation spaces
• Short-circuit of air on indoor,
outdoor units
• Fouling, clogging of heat
exchanger
Note:
RUN light
ON
Green LED
Outdoor
control PCB
Keeps flashing
Yellow LED
Outdoor
Keeps flashing
5. Troubleshooting
* For the contents of control, refer to the protective control by controlling
compressor rotation speed and cooling high pressure protective control of
micro computer control function for corresponding models.
TIMER light
Content
5 times flash
Red LED
1 time flash
Diagnosis
* For the characteristics of discharge
Are the
pipe temperature, refer to E39.
characteristics of
discharge pipe temperature
thermistor
normal?
YES
Is the
discharge pipe
temperature error persisted
during cooling
operation?
NO
Is the
discharge pipe temperature
control normal?
YES
Is the
temperature (measured
actually) at detection of
error correct?
435
435
-
-
-
-
'12 • PAC-T-174
Discharge pipe
temperature error
Countermeasure
Replace discharge pipe
NO
temperature thermistor.
Insufficient refrigerant
YES
amount : Recharge
refrigerant by weighing
proper amount on a scale.
Control operation check *
NO
Defective outdoor control
NO
PCB ➞ Replace.
Check unit side:
YES
• Isn't filter clogged?
• Are adequate indoor,
outdoor unit installation
spaces?
• Isn't there any short-
circuit of air?
• Isn't there any fouling,
clogging on indoor heat
exchanger?