Installation Guide
Nz (neutral zone)
Circuit
2
Set the acceptable flow temperature deviation.
Set the neutral zone to a high value if you can accept a high
variation in flow temperature. When the actual flow temperature
is within the neutral zone, the controller does not activate the
motorized control valve.
Danfoss District Energy
ECL Comfort 210, application A260
12187
Setting range
Factory setting
1 ... 9 K
3 K
The neutral zone is symmetrical around the desired flow temperature
value, i.e. half the value is above and half the value is below this
temperature.
VI.LG.F1.02
DEN-SMT/DK
81