Delay
Circuit
2
If an alarm condition from either 'Upper difference' or 'Lower difference' is
present for a longer time than the set delay (in min.), the alarm function
is activated.
1 ... 99 m: The alarm function will be activated if the alarm
condition remains after the set delay.
Lowest temp.
Circuit
2
The alarm function will not be activated if the desired flow temperature
is lower than the set value.
Danfoss District Energy
ECL Comfort 210, application A260
12149
Setting range
Factory setting
1 ... 99 m
10 m
12150
Setting range
Factory setting
10 ... 50 °C
30 °C
Temp.
If the cause of the alarm disappears, the alarm indication and output
also disappear.