Danfoss ECL Comfort 310 Installation Manual page 15

Hide thumbs Also See for ECL Comfort 310:
Table of Contents

Advertisement

Installation Guide
2.5.2 Electrical connections, 230 V a.c., power supply, pumps, motorized control valves etc.
Application A260
Terminal
Description
16
Alarm
15
14
Phase for circulation pump
13
Do not use
12
P2
Circulation pump ON / OFF, circuit 2
11
P1
Circulation pump ON / OFF, circuit 1
10
Supply voltage 230 V a.c. - neutral (N)
9
Supply voltage 230 V a.c. - live (L)
8
M1
Phase for motorized control valve output, circuit 1
7
M1
Actuator - opening
6
M1
Actuator - closing
5
M2
Phase for motorized control valve output, circuit 2
4
M2
Actuator - opening
3
M2
Actuator - closing
* Relay contacts: 4 A for ohmic load, 2 A for inductive load
Factory established jumpers:
5 to 8, 9 to 14 , L to 5 and L to 9, N to 10
Danfoss District Energy
ECL Comfort 210, application A260
Wire cross section: 0.5 - 1.5 mm²
Incorrect connection can damage the electronic outputs.
Max. 2 x 1.5 mm² wires can be inserted into each screw terminal.
VI.LG.F1.02
Max. load
4 (2) A / 230 V a.c.*
4 (2) A / 230 V a.c.*
4 (2) A / 230 V a.c.*
0.2 A / 230 V a.c.
0.2 A / 230 V a.c.
0.2 A / 230 V a.c.
0.2 A / 230 V a.c.
DEN-SMT/DK
15