Installation Guide
2.5.5 Electrical connections, Pt 1000 temperature sensors and signals
A260:
Terminal
Sensor / description
29 and 30 S1 Outdoor temperature sensor* ESMT
28 and 30 S2 Room temperature sensor**,
circuit 1
27 and 30 S3 Flow temperature sensor***,
circuit 1
26 and 30 S4 Flow temperature sensor***,
circuit 2
25 and 30 S5 Return temperature sensor,
circuit 1
24 and 30 S6 Return temperature sensor,
circuit 2
23 and 30 S7 Flow / heat meter
22 and 30 S8 Room temperature sensor**,
circuit 2
*
If the outdoor temperature sensor is not connected or the
cable is short-circuited, the controller assumes that the
outdoor temperature is 0 (zero) °C.
**
Only for room temperature sensor connection. The room
temperature signal can also be available from a Remote
Control Unit (ECA 30 / 31). See 'Electrical connections, ECA
30 / 31'.
*** The flow temperature sensor must always be connected
in order to have the desired functionality. If the sensor is
not connected or the cable is short-circuited, the motorized
control valve closes (safety function).
Factory established jumper:
30 to common terminal.
20
DEN-SMT/DK
ECL Comfort 210, application A260
Type
(recomm.)
ESM-10
ESM-11 / ESMB /
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
ESM-11 / ESMB /
ESMC / ESMU
ESM-10
VI.LG.F1.02
Danfoss District Energy