Installation Guide
Application Key: Situation 2
The controller already runs an application. The ECL Application
Key is inserted, but the application needs to be changed.
To change to another application on the ECL Application Key, the
current application in the controller must be erased (deleted).
Be aware that the Application Key must be inserted.
Action:
Purpose:
Choose 'MENU' in any circuit
Confirm
Choose the circuit selector at the top
right corner in the display
Confirm
Choose 'Common controller settings'
Confirm
Choose 'Key functions'
Confirm
Choose 'Erase application'
Confirm with 'Yes'
The controller resets and is ready to be configured.
Follow the procedure described in situation 1.