Installation Guide
Input type
Circuit
1
Choice of pulse type from input S7.
OFF:
No input.
IM1:
Pulse.
Units
Circuit
1
Choice of units for measured values.
Units to the left: pulse value.
Units to the right: actual and limitation values.
The value from the flow meter is expressed as ml or l.
The value from the heat meter is expressed as Wh, kWh, MWh or
GWh.
The values for the actual flow and the flow limitation are expressed
as l/h or m³/h.
The values for the actual power and the power limitation are
expressed as kW, MW or GW.
Pulse, ECL Key A2xx
Circuit
1
Set the value of the pulses from the flow / heat meter.
OFF:
No input.
1 ... 9999: Pulse value.
Danfoss District Energy
ECL Comfort 210, application A260
11109
Factory setting
Setting range
OFF / IM1
OFF
11115
Setting range
Factory setting
See the list
ml, l/h
11114
Setting range
Factory setting
OFF / 1 ... 9999
List for setting range of 'Units':
ml, l/h
l, l/h
ml, m³/h
l, m³/h
Wh, kW
kWh, kW
kWh, MW
MWh, MW
MWh, GW
GWh, GW
Example 1:
'Units' (11115):
l, m³/h
10
'Pulse' (11114):
Each pulse represents 10 litres and the flow is expressed as cubic
meters (m³) per hour.
Example 2:
'Units' (11115):
kWh, kW (= kilo Watt hour, kilo Watt)
1
'Pulse' (11114):
Each pulse represents 1 kilo Watt hour and the power is
expressed in kilo Watt.
Example :
One pulse can represent a number of litres (from a flow meter)
or a number of kWh (from a heat meter).
10
VI.LG.F1.02
DEN-SMT/DK
53