Installation Guide
Choosing a heat curve slope
The heat curves represent the desired flow temperature at different outdoor temperatures and at a desired room temperature of 20 °C.
The small arrows ( ) indicate 6 different outdoor temperature values at which you can change the heat curve.
Temp. max. (flow temp. limit, max.)
Circuit
2
Choose the allowed max. flow temperature for your system.
Adjust the factory setting, if required.
Temp. min. (flow temp. limit, min.)
Circuit
2
Choose the allowed min. flow temperature for your system.
Adjust the factory setting, if required.
Danfoss District Energy
ECL Comfort 210, application A260
1.8
2.2
2.6
3.0 3.4
120
110
1.4
100
90
1.0
80
70
0.6
60
50
40
0.2
30
20
10
-30
-20
12178
Setting range
Factory setting
10 ... 150 °C
45 °C
12177
Setting range
Factory setting
10 ... 150 °C
10 °C
-10
0
10
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .
VI.LG.F1.02
20
DEN-SMT/DK