Installation Guide
Choosing a heat curve slope
The heat curves represent the desired flow temperature at different outdoor temperatures and at a desired room temperature of 20 °C.
The small arrows ( ) indicate 6 different outdoor temperature values at which you can change the heat curve.
Temp. max. (flow temp. limit, max.)
Circuit
1
Set the max. flow temperature for the system. The desired flow
temperature will not be higher than this setting. Adjust the factory
setting, if required.
Temp. min. (flow temp. limit, min.)
Circuit
1
Set the min. flow temperature for the system. The desired flow
temperature will not be lower than this setting. Adjust the factory
setting, if required.
Danfoss District Energy
ECL Comfort 210, application A260
1.8
2.2
2.6
3.0 3.4
120
110
1.4
100
90
1.0
80
70
0.6
60
50
40
0.2
30
20
10
-30
-20
11178
Setting range
Factory setting
10 ... 150 °C
90 °C
11177
Setting range
Factory setting
10 ... 150 °C
10 °C
-10
0
10
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .
'Temp. min. ' is overruled if 'Total stop' is active in Saving mode or
'Cut-out' is active.
'Temp. min. ' can be overruled by the influence from the return
temperature limitation (see 'Priority').
The setting for 'Temp. max. ' has higher priority than 'Temp. min. ' .
VI.LG.F1.02
20
DEN-SMT/DK