Technical Specifications - Nibe VPB Installer Manual

Hide thumbs Also See for VPB:
Table of Contents

Advertisement

Technical specifications

VPB 200
Volume
Volume, charge coil
Net weight
Gross weight
Heat transfer (60/50 °C at 50 °C hot water temperature)
Heat content at 50°C
Equivalent amount of hot water (40°C)
Heating time (15 °C to 60 °C) 12 kW charge power
Re-heating time to 60 °C, 70% of the total volume
Max operating temperature
Max pressure, primary side
Max pressure, water heater
Max water supply pressure
Exp. vessle, tap water, charge pressure
Expansion relief valve, setting
Max operating pressure, T&P-valve
Max operating temperature, T&P-valve
Max recommended heat pump size
Part No.
22
Chapter 8 |
Technical data
Stainless
litre
176
litre
7.8
kg
80
kg
260
kW
11.5
kWh
8.2
litre
235
hours
1.12
min.
50
°C
85
bar/MPa
3/0.3
bar/MPa
6/0.6
bar/MPa
16/1.6
bar/MPa
3.5/0.35
bar/MPa
6/0.6
bar/MPa
7/0.7
°C
95
kW
12
088 516
VPB/VPBS UK

Advertisement

Table of Contents
loading

This manual is also suitable for:

Vpbs uk

Table of Contents