MTU 16V4000Lx2x Operating Instructions Manual page 90

Table of Contents

Advertisement

1.4540.022 – Delta P Fail Low
Red alarm. Initiated by TecJet.
Cause
Delta-p from TecJet below the
set limit value.
1.4540.023 – FGP Fail Low
Red alarm. Initiated by TecJet.
Cause
Gas pressure before TecJet is
below the preset limit value.
1.4540.024 – Coil Current Fail Low
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
1.4540.025 – Position Fail Low
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
1.4540.026 – Analog Input Low Error
Red alarm. Initiated by TecJet.
Cause
TecJet setting is not correct.
1.4540.027 – Analog Input High Error
Red alarm. Initiated by TecJet.
Cause
TecJet setting is not correct.
1.4540.028 – PWM Duty Cycle Low Error
Red alarm. Initiated by TecJet.
Cause
TecJet setting is not correct.
90 | Troubleshooting | MS150121/00E 2015-07
Corrective action
u Check TecJet and configuration.
Corrective action
u Check TecJet and configuration.
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.
Corrective action
u Check setting.
Corrective action
u Check setting.
Corrective action
u Check setting.