MTU 16V4000Lx2x Operating Instructions Manual page 68

Table of Contents

Advertisement

112519 – HIHI T-Exhaust B9
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too high in comparison with
weighted average.
112520 – HIHI T-Exhaust B10
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too high in comparison with
weighted average.
112601 – LOLO T-Exhaust A1
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too low in comparison with
weighted average.
112602 – LOLO T-Exhaust A2
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too low in comparison with
weighted average.
112603 – LOLO T-Exhaust A3
Red alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too low in comparison with
weighted average.
68 | Troubleshooting | MS150121/00E 2015-07
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 145).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 145).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check spark plug.
2. Check emission values.
3. Check ignition timing (→ Page 145).
4. Check valve drive.
Corrective action
1. Check spark plug.
2. Check emission values.
3. Check ignition timing (→ Page 145).
4. Check valve drive.
Corrective action
1. Check spark plug.
2. Check emission values.
3. Check ignition timing (→ Page 145).
4. Check valve drive.