1.4540.015 – FGT Fail High
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
1.4540.016 – Delta P Fail High
Red alarm. Initiated by TecJet.
Cause
Differential pressure at TecJet
too high.
1.4540.017 – FGP Fail High
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
1.4540.018 – Coil Current Fail High
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
1.4540.019 – Position Fail High
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
1.4540.020 – Elec Temp Fail Low
Red alarm. Initiated by TecJet.
Cause
Hardware not ready for
operation.
1.4540.021 – FGT Fail Low
Red alarm. Initiated by TecJet.
Cause
Gas temperature before TecJet
is below the preset limit value.
Corrective action
u Restart TecJet.
Corrective action
1. Check gas pressure.
2. Check TecJet for dirt.
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.
Corrective action
u Restart TecJet.
Corrective action
u Check TecJet and configuration.
MS150121/00E 2015-07 | Troubleshooting | 89