112309 – HI T-Exhaust A9
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too high in comparison with
weighted average.
112310 – HI T-Exhaust A10
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too high in comparison with
weighted average.
112311 – HI T-Exhaust B1
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too high in comparison with
weighted average.
112312 – HI T-Exhaust B2
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too high in comparison with
weighted average.
112313 – HI T-Exhaust B3
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too high in comparison with
weighted average.
58 | Troubleshooting | MS150121/00E 2015-07
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 145).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 145).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 145).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 145).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 145).
3. Check valve drive (exhaust valves do not close).