112314 – HI T-Exhaust B4
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too high in comparison with
weighted average.
112315 – HI T-Exhaust B5
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too high in comparison with
weighted average.
112316 – HI T-Exhaust B6
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too high in comparison with
weighted average.
112317 – HI T-Exhaust B7
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too high in comparison with
weighted average.
112318 – HI T-Exhaust B8
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too high in comparison with
weighted average.
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 145).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 145).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 145).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 145).
3. Check valve drive (exhaust valves do not close).
Corrective action
1. Check emission values.
2. Check ignition timing (→ Page 145).
3. Check valve drive (exhaust valves do not close).
MS150121/00E 2015-07 | Troubleshooting | 59