112409 – LO T-Exhaust A9
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too low in comparison with
weighted average.
112410 – LO T-Exhaust A10
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too low in comparison with
weighted average.
112411 – LO T-Exhaust B1
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too low in comparison with
weighted average.
112412 – LO T-Exhaust B2
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too low in comparison with
weighted average.
112413 – LO T-Exhaust B3
Yellow alarm. Initiated by EMU.
Cause
Individual exhaust gas
temperature of this cylinder is
too low in comparison with
weighted average.
62 | Troubleshooting | MS150121/00E 2015-07
Corrective action
1. Check spark plug.
2. Check emission values.
3. Check ignition timing (→ Page 145).
4. Check valve drive.
Corrective action
1. Check spark plug.
2. Check emission values.
3. Check ignition timing (→ Page 145).
4. Check valve drive.
Corrective action
1. Check spark plug.
2. Check emission values.
3. Check ignition timing (→ Page 145).
4. Check valve drive.
Corrective action
1. Check spark plug.
2. Check emission values.
3. Check ignition timing (→ Page 145).
4. Check valve drive.
Corrective action
1. Check spark plug.
2. Check emission values.
3. Check ignition timing (→ Page 145).
4. Check valve drive.