CleaverBrooks FLX Operation, Service And Parts Manual page 49

Packaged boiler
Table of Contents

Advertisement

Profire V Burner
PROBLEM
Burner Stays in Low-Fire
PROBLEM
Shutdown Occurs During Firing
750-177
1.
Pressure or temperature above modulating control setting.
2.
Manual-automatic switch in wrong position.
3.
Inoperative modulating motor.
4.
Defective modulating control.
5.
Binding or loose linkages, cams, setscrews, etc.
1.
Loss or stoppage of fuel supply.
2.
Defective fuel valve, loose electrical connection.
3.
Flame detector weak or defective.
4.
Scanner lens dirty or sight tube obstructed.
5.
If the programmer lockout switch has not tripped, check the limit circuit for an
opened safety control.
6.
If the programmer lockout switch has tripped:
a. Check fuel lines and valves.
b. Check flame detector.
c. Check for open circuit in running interlock circuit.
d. The flame failure light is energized by ignition failure, main flame failure, inad-
equate flame signal, or open control in the running interlock circuit.
7.
Improper air/fuel ratio.
a. Slipping linkage.
b. Damper stuck open.
c. Fluctuating fuel supply.
•Temporary obstruction in the fuel line.
•Temporary drop in gas pressure.
8.
Interlock device inoperative or defective.
9.
air in the oil lines. Bleed lines.
SOLUTION
SOLUTION