Chapter 2
LOW-HIGH-LOW MOD - OPEN DAMPER PURGE
COMPONENTS
DESCRIPTION
PRE-PURGE
STARTUP,
IGNITION
RUN,
MODULATE
SHUT DOWN,
POST-PURGE
VARIATIONS
2-14
Combustion Air
A
two
blade
damper
controlled by a two position,
spring
return
actuator
with
mechanical linkage. Power to
drive the actuator is routed
through a low/auto switch and a
remote
located
modulating
control.
The
actuator
also
contains a limit switch which is
used to actuate the second
stage of the oil supply system.
(see oil at right) A second
external switch ensures the
damper has returned to the low
fire position before ignition is
initiated.
From its closed position the
damper is driven open by the
flame safeguard control where
it remains for the duration of the
pre-purge cycle.
Damper returns to the low fire
position
which
is
proven
through the external switch.
The burner is now ready for
startup.
Damper is driven open in 30
seconds by the two position
actuator.
Low-High-Low
burners will modulate from low
to high rate positions based on
the signal from the modulating
control and the selection of the
low/auto switch.
Damper returns to its start
position
based
on
the
25
second closure speed of the
mechanical actuator.
None
Gas
is
Safety shut off valve(s) are
provided to initiate the flow of
gas. The primary is a diaphragm
or motorized type valve which
have delayed opening rates to
prevent an "in rush" of gas. A
butterfly type gas metering valve
is linked directly to the damper
actuator and provides gas flow
metering during the drive to the
high
position.
A
manually
adjusted gas regulator limits
maximum firing rate.
Valves are closed.
Valves open. To prevent a surge
the primary gas valve opens at a
slowed rate. Gas flow to the
manifold is metered based on
the butterfly valves low fire
setting.
The gas valves remain in their
open
position.
The
actuator
begins its travel to the high fire
position
opening
the
metering valve. The burner will
modulate from low to high as
described in the combustion air
column.
On shut down all gas valves
close within 1 second. The
butterfly valve closes in 25
seconds with the two position
actuator.
None
Profire V Burner
Oil
Pressure Atomization: Two solenoid type safety
shut off oil valves initiate the flow of oil from the high
pressure pump to the nozzle. The oil pump has a
built in solenoid controlled two level pressure
regulating system. Low and high flow rates are set
on the pump based on pressure and the nozzle's
flow
rating.
The pump is operational but the valves are closed.
Oil is flowing through an internal relief valve and
returning to the supply system.
Safety shut off valves open allowing oil to flow from
pump to nozzle. Oil pressure at the nozzle is based
on the pump's low pressure setting. Excess oil is
flowing through an internal relief valve and returning
to the supply system.
The safety shut-off oil valves remain open. The
pump's solenoid is energized by the aux switch
within the damper actuator as it opens the air
gas
damper. Oil pressure is then increased based the
pump's high pressure setting. The actuator begins
its travel to the high fire position opening the gas
metering valve. The burner will modulate from low
to high as described in the combustion air column.
All valves immediately return to their startup or de-
energized position. The oil pump is operating with
post-purge, but oil is flowing through an internal
relief valve and returning to the supply system.
For pumps without the internal dual pressure
solenoid an external pressure relief valve and
normally
open
used.
solenoid
valve
are
750-177