iControl Manual
get voltage
get device <#1‐#16/devname> voltage
set main a vcalibration <nnn.nn>
get voltage alarm
get device <#1‐#16/devname> voltage alarm
set main a hvalarm <nnn>
set device <#1‐#16/devname> main a
hvalarm <nnn>
set main a lvalarm <nnn>
set device <#1‐#16/devname> main a
lvalarm <nnn>
get console
set console timeout <30‐3600/disable>
set console baudrate
<400/4800/9600/19200/38400/57600/115200>
get modem
set modem countrycode <countrycode>
set device <0‐16>
get device
Get the measured voltage of the local iControl.
Get the measured voltage of the selected iControl.
Set the voltmeter calibration. From 105.00 to 150.00 in 0.01 V
increments.
High and Low alarms are used to monitor voltage conditions and send
an alert by email, SNMP and syslog when the high or low thresholds
are exceeded.
Adjustable in 1 V increments.
Displays the current console configuration, Timeout, and Baud Rate.
Console can be set to automatically logout with no activity for 30
seconds to 1 hr in seconds, or disabled.
The baud rate of the serial port.
400,4800,9600,19200,38400,57600,115200 bps
Gets the current settings of the modem. (modem models only)
Sets the modem country code. (modem models only)
See Appendix for a list of country codes.
Get / Set the device ID for cluster applications. Set a device ID of 0 for
single iControl applications. A device ID of 1 makes the unit a master,
and a device ID of 2-16 makes the iControl a remote in cluster
configurations. These commands are only valid when directly
connected to the iControl, rather than as remote units in a cluster.
17
Yes
Yes
Yes
Highalarm:
135-150 V
Lowalarm:
90-105 V
Yes
Yes
120
Yes
115200
Yes
Yes
181 (USA)
Yes
0