Manual INTRODUCTION ® The SurgeX iControl SX-1115ip-X (SX-1120ip-X) is a single rack-space, 120V, 15 (20) amp, AC power conditioner that can be controlled over a network or the internet. The iControl ® incorporates SurgeX Advanced Series Mode power conditioning and surge elimination, as well ®...
Page 5
Setup and Control functions can be linked to any SNMP v1 compatible manager. The iControl MIB is available at surgex.com. All activity can be reported to a syslog compatible server. The iControl’s internal web server is secured with Secure Sockets Layer (SSL) encryption.
7. Upload modified configurations to iControls. 8. Control outlets on one or more iControls throughout the network. The iControl Setup and Control utility is available on the iControl CD or on the SurgeX website http://www.surgex.com Note: The Setup and Control Utility only operates with iControls attached to the network.
iControl Manual Command Line Interface (CLI) All configuration parameters are set using the Command Line Interface (CLI). The CLI is accessed through the network, using a telnet client, or through the serial port, or data modem (for models with internal modem option) using a terminal client. In iControl clusters, all remote iControls can be configured and managed through the connection to the Master iControl.
Page 8
iControl Manual Setting the IP address using CLI These are the basic commands to set the network parameters. After setting these parameters, the iControl will need to be rebooted for the settings to take effect. Any command that requires rebooting of the iControl will provide a prompt to do so. All commands may be entered as required before rebooting.
Page 9
iControl Manual Setting the IP address using ARP / Ping The ARP / Ping technique uses a PC running a command line (DOS Window) to set the IP Address. To set the IP address using ARP, connect the iControl to your local network and apply power.
Manual INSTALLATION The SurgeX iControl is designed to be installed in a 19 inch equipment rack and requires one unit (1-U) of rack space. Use the four screws provided with the product to secure the rack ears to the rack rails. These screws can be tightened by hand and do not require tools. Connect power to the unit by plugging the cord into a 120V AC, 20 amp wall or floor receptacle.
iControl Manual LED INDICATORS There are two LED indicators located on the front panel. Their function is as follows: Self Test (Green): When illuminated, the surge suppression circuitry is functioning correctly. Power (Red): When illuminated, the iControl is connected to a live wall or floor outlet. WEB SERVER The iControl web interface provides the easiest means of operating the outlets and monitoring the current status of the units.
iControl Manual Control The Control panel provides the clickable buttons to change the status of one or more outlets. Once one or more outlets have been selected, click on the On, Off, or Cycle button. Cycle will perform a timed change in outlet state;...
iControl Manual Outlet Status Outlet Status is displayed by a colored text box. The color indicates the current status of the outlet, and the text indicates the function being performed. High current or voltage alarms are highlighted in red; low current or voltage alarms are highlighted in yellow.
iControl Manual AutoPing View The AutoPing View displays the 16 AutoPing channels, their programmed action, and current status. The status column will display the current status of the AutoPing. The numeric column will display the number of times the AutoPing has been triggered. A numeric counter other than 0, with the status reporting OK, indicates that there have been previous AutoPing triggers, but the current status is OK.
iControl Manual COMMAND LINE INTERFACE (CLI) PROTOCOL The Command Line Interface provides complete setup of all functions of the iControl. The CLI may be accessed either via the network interface using Telnet, or via the modem (for models with internal modem option) or serial port using a terminal emulator program.
iControl Manual User Commands Command Description Admin Fact Def get users Return a list of all current users. get user <username> Returns the selected user’s details. add user <username> Added a user to the root iControl’s user table. 16 users maximum.
iControl Manual Device Commands Command Description Admin Fact Def get devices / get all / get outlets This command displays a list of connected devices, and their current status. Get device information. Displays the device name, and all outlet iControl get device <#1‐#16/devname>...
Page 18
iControl Manual get voltage Get the measured voltage of the local iControl. get device <#1‐#16/devname> voltage Get the measured voltage of the selected iControl. set main a vcalibration <nnn.nn> Set the voltmeter calibration. From 105.00 to 150.00 in 0.01 V increments.
iControl Manual Sets the ID of a remote device in cluster configurations. The hardware set unit <hwkey> device <2‐16> key <hwkey> is the last 2 bytes of the MAC address with NO spaces, dashes or colons. In this example, the <hwkey>...
Set the root iControl’s web server’s port. Web standard port is 80. If set web port <1‐65535> changed, access the iControl using http://xxx.xxx.xxx.xxx:<port> SurgeX recommends changing the web port on all iControls that are accessible from the internet. set web ssl <yes/no>...
iControl Manual Autoping Commands Command Description Admin Fact Def get autoping <1‐16> Returns the settings and state of the selected autoping. set autoping <1‐16> ipaddress <dotted decimal> Set the IP address of the selected autoping in dotted 0.0.0.0 decimal. set autoping <1‐16> action <action> Set the action of the selected autoping.
iControl Manual set event < eventname> month <1‐12> Sets the month of the event. set event <eventname> day <1‐31> Sets the day of the event. set event <eventname> hour <0‐23> Sets the hour of the event. set event <eventname> minute <0‐59> Sets the minute of the event.
iControl Manual Time Commands Command Description Admin Fact Def get time Returns the current time and NTS settings. set time server <ip address> Sets the address of an NTS server for the root iControl to query. 129.6.15.29 set time usents <yes/no> Enables or disables the root iControl’s ability to connect to an NTS.
iControl Manual ADVANCED OPERATION DTMF Control The iControl can be controlled from dial up connections using handset dialing tones (touch tones). Use of DTMF control requires a unique PIN number set for each user. This PIN is set using the command line interface, and must be 4 to 10 digits long. Program a PIN code of 0 to disable a user’s ability to use DTMF control.
iControl Manual Timed Events The iControl provides the ability to turn On, Off, or Cycle outlets based on time and date. Each individual outlet or group can be set to operate a selected command at a specific time and date. The Timed Events are programmed through the Setup &...
iControl Manual AutoPing The AutoPing feature allows the iControl to automatically detect failed equipment and perform a timed reboot or other power control function (like turning on an indicator or siren). Set any IP address to be periodically pinged. When the iControl no longer detects a response from the address, the programmed power control function is actuated.
iControl Manual CLI Operation and Setup To view the status of any of the AutoPing channels, issue the get autoping <1‐16> command. iControl > get autoping 1 IP Address: 192.168.1.7 Action: Cycle Outlet: Cabinet_1 ‐ Firewall Frequency: 30 Count: 3 Status: OK iControl >...
iControl Manual CERTIFICATE UPLOAD UTILITY The Certificate Utility (CUU.exe) is designed to create and distribute Secure Socket Layer (SSL) certificates to iControls and the PCs that communicate with them. Although the iControl comes from the factory with a certificate installed, this certificate will generate a warning message when connecting to the iControl when using SSL. For most customers, this error message can be easily ignored and secure connection to the iControl continues.
Emails generated by the iControl will display the device, outlet(s) command, and the user and method of control. Examples: Subject : Power Switch: Cabinet_1 Date : Mon, 7 Jul 2008 09:41:00 - 0500 From : <iControl@surgex.com> networkadmin@yourco.com Location: Cabinet_1 Outlets: 5 Server_B Command: Cycle User: admin Source: Telnet...
The iControl can be upgraded via the network if the upload feature has been enabled using the set upload enable yes command on the console interface. To upgrade the iControl, download the latest version of the firmware and upgrade utility from the SurgeX website. http://www.surgex.com...
PC running Windows 98 or higher and the iControl. Administrator rights are required on the iControl to properly use the Utility. All communication between the program and the iControl is encrypted using AES. The iControl Setup and Control Utility is available on the iControl CD or on the SurgeX website http://www.surgex.com.
iControl Manual COMPLIANCE STATEMENTS FCC Part 15 Regulation This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part 15 of the FCC rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation.