Device Commands - SurgeX SX-1115ip-X User Manual

Web-enabled power conditioning management system
Table of Contents

Advertisement

iControl Manual

Device Commands

Command
get devices / get all / get outlets
get device <#1‐#16/devname>
set device <#1‐#16 > name <name>
get cycle
set cycle <1‐99>
get delay
set delay <1‐99>
get power
get current
get device <#1‐#16/devname> current
get current alarm
get device <#1‐#16/devname> current alarm
set main a hcalarm <nn.n>
set device <#1‐#16/devname> main a
hcalarm <nn.n>
set main a lcalarm <nn.n>
set device <#1‐#16/devname> main a
lcalarm <nn.n>
Description
This command displays a list of connected devices, and their current
status.
Get device information. Displays the device name, and all outlet
names and current status.
Set the name of the selected iControl. 20 characters max.
Get or set the cycle time in seconds.
Get or set the delay time in seconds.
Get the current power draw and energy used since the last counter
reset. The energy counter can be reset via SCU or web page, and will
also reset after a reboot.
Get the measured current of the local iControl.
Get the measured current of the selected iControl.
High and Low alarms are used to monitor current conditions and send
an alert by email, SNMP and syslog when the high or low thresholds
are exceeded.
From 0.0 to 10.0/15.0/20.0 (depending on max current for device) in
0.1 amp increments.
16
Admin
Fact Def
No
Yes
iControl
No
10
No
1
Yes
Yes
Highalarm:
15.0 for 15
Amp Models
20.0 for 20
Amp Models
Lowalarm:
0.0 Amp