13. Manually decrease the ring rate by 500 rpm increments observing
combustion down to the low re rpm setting (minimum) on the factory
test re sheet. If required low re combustion may be altered by adjusting
the o set adjustment screw with either a Torx®T40 or a 5mm hex wrench.
NOTE: Turning the screw counterclockwise decreases gas ow, clockwise
increases gas ow.
14. Before leaving the "Firing Rate" screen, tap "Automatic" ring rate control.
Do not leave the unit in the "Manual in Run" mode.

Shut Down Procedures

Normal Shut Off Procedures
1. Place the local/o /remote switch in the o position.
2. Close all manual gas valves.
3. Turn o electrical power.
Emergency Shut Off Procedures
The main gas cock should be closed immediately. If overheating occurs or the gas
supply fails to shut o , do not turn o or disconnect the electrical supply to the
pump. Instead, shut o the gas supply at a location external to the boiler.

Shutting the Boiler Down for an Extended Period of Time

If the boiler is to be shut o for a period greater than 3 months:
1. Perform normal shut down procedure
2. Isolate water supply and ow circuit from boiler
3. Drain boiler
4. Disconnect electrical supply

Starting Boiler After Prolonged Shutdown

Perform initial start up procedures as described in this manual.

SOLA Control Features

Flame Detection

The ame signal can be viewed from the Main Screen and the Status Detail
screen on the Control. See Figure 13.
Questions? Call (315) 298-5121, or visit us online at www.fulton.com
OPERATION
!
WARNING
All information in this manual is for
reference and guidance purposes,
and does not substitute for required
professional training, conduct, and strict
adherence to applicable jurisdictional/
professional codes and regulations.
4
CAUTION
Only factory-trained personnel should
attempt to alter password protected Control
preset values.
3-7