Download Print this page

Carrier 59SP5A Installation, Start-Up, Operating And Service And Maintenance Instructions page 65

100 series

Advertisement

SERVICE
AND
MAINTENANCE
PROCEDURES
FIRE,
INJURY
OR DEATH
HAZARD
Failure
to follow
this warning
could
result
in personal
iniury,
death and/or property
damage.
The
ability
to
properly
perform
maintenance
on
this
equipment
requires
certain
knowledge,
mechanical
skills,
tools,
and equipment.
If you do not possess
these, do not
attempt
to perform
any service
and maintenance
on this
equipment
other than those procedures
recommended
in the
Owner's
Manual.
ENVIRONMENTAL
HAZARD
Failure to follow this caution may result in environmental
pollution.
Remove and recycle all components or materials (i.e. oil,
refrigerant, control board, etc.) before unit final disposal.
ELECTRICAL
SHOCK,
FIRE
OR
EXPLOSION
HAZARD
Failure
to follow
this warning
could
result
in personal
injury or death, or property
damage.
Before
installing,
modifying,
or servicing
system,
main
electrical
disconnect
switch
must be in the OFF position
and
install
a lockout
tag.
There
may
be
more
than
one
disconnect
switch.
Lock
out and tag switch
with a suitable
warning
label.
Verify proper operation
after servicing.
ELECTRICAL
OPERATION
HAZARD
Failure
to follow
this caution
may
result
in
improper
furnace
operation
or failure of furnace.
Label
all wires
prior
to
disconnection
when
servicing
controls.
Wiring
errors can cause
improper
and dangerous
operation.
General
These
instructions
are written
as if the furnace
is installed
in an
upflow
application.
An upflow
furnace
application
is where
the
blower
is located
below the combustion
and controls
section
of the
furnace,
and
conditioned
air is discharged
upward.
Since
this
furnace
can be installed
in any of the 4 positions
shown
in Fig. 2,
you
must
revise
your
orientation
to
component
location
accordingly.
Electrical
Controls
and Wiring
ELECTRICALSHOCK
HAZARD
Failure
to follow
this warning
could result in personal
iniury
or death.
There may be more than one electrical
supply
to the furnace.
Check
accessories
and cooling
unit for additional
electrical
supplies
that must be shut off during
furnace servicing.
Lock
out and tag switch with a suitable warning
label.
The electrical ground and polarity for 115-v wiring must be
properly maintained. Refer to Fig. 34 for field wiring information
and to Fig. 63 for furnace wiring information.
NOTE:
If the polarity is not correct, the STATUS LED on the
control will flash rapidly and prevent the furnace from heating. The
control system also requires an earth ground for proper operation
of the control and flame-sensing
electrode.
The 24-v circuit contains an automotive-type,
3-amp. fuse located
on the control. (See Fig. 35.) Any shorts of the 24-v wiring during
installation, service, or maintenance will cause this fuse to blow. If
fuse replacement is required, use ONLY a 3-amp. fuse. The control
LED will display status code 24 when fuse needs to be replaced.
Troubleshooting
Refer to the service label. (See Fig. 54--Service
Label.)
The Troubleshooting
Guide (See Fig. 62) can be a useful tool in
isolating
furnace operation problems. Beginning
with the word
"Start," answer each question and follow the appropriate arrow to
the next item.
The Guide will help to identify the problem or failed component.
After replacing any component, verify correct operation sequence.
Proper instrumentation
is required to service electrical controls.
The control in this furnace is equipped with a Status Code LED
(Light-Emitting
Diode)
to aid in installation,
servicing,
and
troubleshooting.
Status codes can be viewed at the indicator in
blower
door. The amber furnace control LED
is either ON
continuously,
rapid flashing, or a code composed of 2 digits. The
first digit is the number of short flashes, the second digit is the
number of long flashes.
For an explanation of status codes, refer to service label located on
control door or Fig. 54, and the troubleshooting
guide which can
be obtained from your distributor.
Retrieving
Stored
Fault
Codes
NOTE:
Fault codes cannot be retrieved if a thermostat signal
(24-v on W, Y, G, etc.) is present, or if any delays such as blower
off-delays are active.
The stored status codes will NOT be erased from the control
memory when 115- or 24-v power is interrupted. See the Service
Label (Fig. 54) for more information. The most recent fault code
may be retrieved as follows:
1. Leave 115-v power connected to furnace.
2. Observe the status LED through the blower door (the lower
door on upflow applications) indicator. Refer to the Service
Label (Fig. 54) to interpret the LED.
3. Remove the Main/Control door (the upper door on upflow
installations).
4. BRIEFLY disconnect and reconnect ONE of the main limit
wires.
5. The LED will flash the last stored fault code. Refer to the
Service Label (Fig. 54) to interpret the LED.
6. A component test sequence will follow.
7. Reinstall the Main/Control door.
ii
65

Advertisement

loading