Download Print this page

Carrier 59SP5A Installation, Start-Up, Operating And Service And Maintenance Instructions page 39

100 series

Advertisement

5. Termination or termination kit should be positioned where
vent vapors are not objectionable.
Direct Vent / 2-Pipe
System
Direct vent (2-pipe) vent and combustion air pipes must terminate
outside the structure. Follow all clearances as shown Fig 45.
Allowable vent and combustion air terminations are shown in Fig.
47.
Ventilated
Combustion
Air
The vent
pipe
for a Ventilated
Combustion
Air
System
must
terminate
outdoors.
Follow
all vent termination
clearances
shown
in Fig 46. Allowable
vent terminations
are shown
in Fig 48. The
combustion
air pipe terminates
in a well-ventilated
attic or crawl
space. Follow
the clearances
as shown
in Fig. 50.
The combustion
air pipe cannot
terminate
in attics or crawl spaces
that use ventilation
fans designed
to operate
in the heating
season.
If ventilation
fans are present
in these
areas,
the combustion
air
pipe must terminate
outdoors
as a Direct
Vent System.
Non-Direct Vent / 1-Pipe System
The
vent
pipe
for
a Non
Direct
Vent
(I-pipe)
system
must
terminate
outdoors.
Follow
all vent termination
clearances
shown
in Fig 46. Allowable
vent terminations
are shown
in Fig. 48
A combustion
air pipe
to the
outdoors
is not required
for
a
Non-Direct
Vent System.
A 12-in.
long
section
of pipe
with
a
tight radius
2-in.
(50.8
mm)
90 degree
elbow
is required
to be
attached
to the furnace.
Termination
Requirements
for the Provinces
of Alberta
and
Saskatchewan
The Provinces
of Alberta
and Saskatchewan
require
a minimum
unobstructed
distance
of 4 ft. (1.2 M) from the foundation
to the
property
line
of the
adjacent
lot
for vent
termination
of any
appliance
with an input over 35,000
btuh. If there is less than 4 ft.
(1.2
M)
of unobstructed
distance
to
the
property
line
of the
adjacent
lot, no type of vent termination
is permitted
for appliances
with inputs greater
than 35,000
btuh.
There
are
no additional
restrictions
on
unobstructed
distances
greater than 8 ft. (2.4 M). All single, two-pipe
and concentric
vents
nmy
be
used,
providing
all
other
Code
and
manufacturer's
requirements
in these
instructions
are adhered
to. Refer
to the
appropriate
Vent Termination
section
above for locating
the vent
termination
If the unobstructed
distance
from
the foundation
to the property
line of the adjacent
lot is no less than 4 ft. (1.2 M) and no greater
than 8 ft. (2.4 M), it will be necessary
to re-direct
the flue gas
plume.
In this situation,
a concentric
vent kit cannot
be used.
A
2-pipe termination
(or single pipe termination
when permitted)
that
re-directs
the flue gas away by use of an elbow
or tee, certified
to
ULC $636 from the adjacent
property
line must be used.
See Fig.
49.
The concentric
vent kit currently
cannot be modified
to attach an
elbow to the vent portion
of the rain cap. A tee attached
to the rain
cap could potentially
direct the flue gas plume toward
the intake air
stream
and
contaminate
the
incoming
combustion
air
for the
furnace.
Refer to Fig. 49 for terminations
approved
for use in Alberta
and
Saskatchewan.
Size the Vent and Combustion
Air Pipes
General
Furnace
combustion
air and vent
pipe connections
are sized
for
2-in. (51 mm)
pipe. Any pipe
diameter
change
should
be made
outside
furnace
casing
in vertical
pipe. Any change
is diameter
to
the pipe
must
be
made
as close
to the furnace
as reasonably
possible.
The Maximum
Vent Length
for the vent and combustion
air pipe
(when
used)
is determined
from
the Maximum
Equivalent
Vent
Length
in Table 13 or 15, minus
the number
of fittings
multiplied
by the deduction
for each type of fitting used from Table 14.
The measured
length
of pipe used in a single or 2-pipe
termination
is included
in the total vent length.
Include
a deduction
for a Tee
when
used for Alberta
and Saskatchewan
terminations.
Concentric
vent
terminations,
pipe
lengths
or
elbows
do
not
require
a
deduction
from the Maximum
Equivalent
Vent Length.
1. Measure
the individual
distance
from the furnace
to the ter-
mination
for each pipe.
2. Select a Maximum
Equivalent
Vent Length
(MEVL)
longer
than the measured
distance
of the individual
vent and com-
bustion
air connections
to the vent termination.
3. Count the number
of elbows
for each pipe.
4. For each pipe, multiply
the number
of elbows
by the equi-
valent
length
for the type of elbow
used.
Record
the equi-
valent
length of all the elbows
for each pipe.
5. If a Tee is used on the termination,
record
the equivalent
length of the Tee used.
6. Record
the equivalent
length
of the termination
to be used.
7. Subtract
the equivalent
lengths
of the fittings
and termina-
tions from the Maximum
Equivalent
Vent Length.
8. If the Maximum
Vent Length
calculated
is longer
than the
individual
measured
length
of the vent pipe and combustion
air pipe, then the diameter
of pipe selected
may be used.
9. If the Maximum
Vent Length
calculated
is shorter
than the
individual
measured
length
of either
the vent pipe
or the
combustion
air pipe, recalculate
the Maximum
Vent Length
using the next larger diameter
pipe.
NOTE:
The vent pipe and combustion
air pipe must be the same
diameter.
NOTE:
If the Maximum
Vent Length
for diameter
of the pipe
selected
is longer
than
the measured
length
and the equivalent
length
of all the fitting
and terminations,
recalculate
using the next
smaller
diameter.
If the recalculated
Maximum
Vent
Length
is
longer
than the measured
length
of the vent pipe and combustion
air pipe, then that diameter
of pipe selected
may be used.
When installing
vent systems
of short pipe lengths,
use the smallest
allowable
pipe diameter.
Do not use pipe size greater
than required
or
incomplete
combustion,
flame
disturbance,
or
flame
sense
lockout
may occur.
Combustion
Air and Vent Piping Insulation
Guidelines
NOTE:
Use closed cell, neoprene
insulation
or equivalent.
The vent pipe may pass through
unconditioned
areas. The amount
of exposed
pipe allowed
is shown
in Table 12.
1. Using winter design
temperature
(used in load calculations),
find appropriate
temperature
for your
application
and fur-
nace model.
2. Determine
the amount
of total and exposed
vent pipe.
3. Determine
required
insulation
thickness
for exposed
pipe
length(s).
4. When combustion
air inlet piping
is installed
above
a sus-
pended
ceiling,
the pipe MUST
be insulated
with moisture
resistant
insulation
such
as Armaflex
or other
equivalent
type of insulation.
5. Insulate
combustion
air inlet piping when
run in warm, hu-
mid spaces.
6. Install
the insulation
per the insulation
manufacturer's
in-
stallation
instructions.
NOTE:
Pipe length
(ft. / M) specified
for maximum
pipe lengths
located
in unconditioned
spaces
cannot exceed
total allowable
pipe
length
as calculated
from Table 13 or 15.
ii
39

Advertisement

loading