Download Print this page

Carrier 59SP5A Installation, Start-Up, Operating And Service And Maintenance Instructions page 20

100 series

Advertisement

ii
Attach
tube
to condensate
trap
\
Cut formed end off
\
condensate
drain
tube
\
\
Field supplied
1/2"CPVC
Connect short end _
_]_
_7UlPl_l,_g2t,drnainexten,sion
of"Z"pipetomodified\_
\"
i_
TRAP,
DRA_N
ELBOW
WiTH
D_SCHARGE
P_PE
Field supplied
1/2"
CPVC to drain
Modified drain tube connect to
condensate trap and"Z" pipe
ommet
from
loose parts bag
Field-supplied
1/2"CPVC coupling
& drain
pipe 17 1/2'; 21"and 24 1/2"casings
LEFT SIDE DRAIN ROUTED BEHIND INDUCER
A11344
Fig. 16 - Drain Trap Connection and Routing
trap
Horizontal
Drain Trap Grommet
Fig. 17 - Horizontal
Drain
Trap
Grommet
Al1348
INSTALLATION
Upflow
Installation
NOTE:
The furnace nmst be pitched forward as shown in Fig. 23
for proper condensate drainage.
Supply
Air Connections
For a furnace not equipped with a cooling coil, the outlet duct shall
be provided with a removable access panel. This opening shall be
accessible when the furnace is installed and shall be of such a size
that the heat exchanger can be viewed for possible openings using
light assistance or a probe can be inserted for sampling the air
stream. The cover attachment shall prevent leaks.
Connect supply-air
duct to flanges on furnace supply-air
outlet.
Bend flange upward to 90 ° with wide duct pliers. (See Fig. 20.)
The supply-air
duct must be connected
to ONLY the furnace
supply-outlet-air
duct flanges or air conditioning
coil casing
(when used). DO NOT cut main furnace casing side to attach
supply air duct, hunfidifier, or other accessories. All accessories
MUST be connected to duct external to furnace main casing.
Return
Air Connections
FIRE
HAZARD
A failure to follow
this warning
could cause personal
iniury,
death and/or property
damage.
Never
connect
return-air
ducts to the back of the furnace.
Follow
instructions
below.
The return-air
duct nmst be connected to bottom, sides (left or
right), or a combination
of bottom and side(s) of main furnace
casing. Bypass hunfidifier may be attached into unused return air
side of the furnace casing. (See Fig. 24, 25, 26.)
Bottom Return Air Inlet
These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. Remove and discard this panel when
bottom return air is used. To remove bottom closure panel, perform
the following:
1. Tilt or raise furnace and remove 4 screws holding bottom
plate. (See Fig. 22.)
2. Remove bottom plate.
3. Remove bottom closure panel.
4. Reinstall bottom plate and screws.
Side Return Air Inlet
These furnaces are shipped with bottom closure panel installed in
bottom return-air opening. This panel MUST be in place when
only side return air is used.
NOTE:
Side return-air openings can be used in UPFLOW and
some HORIZONTAL
configurations.
Do not use side return-air
openings in DOWNFLOW configuration.
(See Fig. 24, 25, 26.)
Leveling Legs (If Desired)
In upflow position with side return inlet(s), leveling legs may be
used. (See Fig. 21.) Install field-supplied,
5/16 x 1-1/2 in. (8 x 38
ram) (max) corrosion-resistant
machine bolts, washers and nuts.
NOTE:
Bottom closure nmst be used when leveling legs are used.
It may be necessary to remove and reinstall bottom closure panel to
install leveling legs. To remove bottom closure panel, see Item 1 in
Bottom Return Air Inlet section in Step 1 above.
To install leveling legs:
1. Position furnace on its back. Locate and drill a hole in each
bottom corner of furnace.
2. For each leg, install nut on bolt and then install bolt with
nut in hole. (Install flat washer if desired.)
3. Install another nut on other side of furnace base. (Install flat
washer if desired.)
4. Adjust outside nut to provide desired height, and tighten in-
side nut to secure arrangement.
5. Reinstall bottom closure panel if removed.
Downflow
Installation
NOTE:
The furnace nmst be pitched forward as shown in Fig. 23
for proper condensate drainage.
Supply
Air Connections
NOTE:
For downflow @plications, this furnace is @proved for
use on combustible
flooring when any one of the following 3
accessories are used:
• Special Base, KGASB
• Cased Coil Assembly Part No. CNPV, CNRV, CAP, or CAR
• Coil Box Part No. KCAKC
1. Deternfine
application
being installed
from Table 6.
2. Construct
hole in floor per Table 6 and Fig. 19.
2O

Advertisement

loading