Download Print this page

Carrier 59SP5A Installation, Start-Up, Operating And Service And Maintenance Instructions page 21

100 series

Advertisement

3.Construct
plenum todimensions
specified in Table 6 and
Fig. 1 9.
4.Install special base coil a ssembly
orcoil b oxas shown in in
Fig. 1 9.
NOTE:It is recommended
thattheperforated
supply-air duct
fanges b ecompletely
removed from furnace when i nstalling the
furnace onafactory-supplied
cased coil o rcoil b ox. Toremove the
supply-air duct f lange, use wide duct p liers orhand s eamers
to
bend f lange b ack a nd forth until i t breaks off.Be careful ofsharp
edges. (See F ig. 2 0.)
FIRE,EXPLOSION, AND CARBON MONOXIDE
POISONING
HAZARD
Failure t o follow thiswarning c ould result i n personal
injury, death, orproperty damage.
Donot i nstall the furnace onitsback o rhang f urnace with
control compartment
facing downward. Safety c ontrol
operation will be adversely affected. Never c onnect
return-air ducts tothe back o fthe furnace.
CUT HAZARD
Failure
to follow
this caution
may result in personal
iniury.
Sheet
metal parts may have sharp edges
or burrs.
Use care
and wear
appropriate
protective
clothing,
safety glasses
and
gloves
when handling
parts, and servicing
furnaces.
Connect
supply-air
duct
to supply-air
outlet
on furnace.
Bend
flange
inward
past 90 ° with wide
duct pliers
(See Fig. 20.) The
supply-air
duct nmst
be connected
to ONLY
the furnace
supply
outlet or air conditioning
coil casing
(when
used). When
installed
on combustible
material,
supply-air
duct
must
be connected
to
ONLY
the
factory-approved
accessory
subbase,
or
a
factory-approved
air conditioning
coil casing.
DO NOT
cut main
furnace
casing to attach supply
side air duct, hunfidifier,
or other
accessories.
All accessories
MUST
be connected
to duct external
to
furnace
casing.
Return
Air
Connections
FIRE
HAZARD
A failure to follow
this warning
could cause personal
injury,
death and/or property
damage.
Never
connect
return-air
ducts
to the back of the furnace.
Follow
instructions
below.
The
return-air
duct
nmst
be
connected
to return-air
opening
(bottom
inlet).
DO
NOT
cut
into
casing
sides
(left or right).
Bypass
hunfidifier
connections
should be made at ductwork
or coil
casing sides exterior to furnace.
(See Fig. 25.)
Bottom
Return
Air Inlet
These furnaces are shipped
with bottom
closure
panel installed in
bottom
return-air
opening.
Remove
and discard this panel when
bottom
return air is used. To remove
bottom closure
panel, perform
the following:
1. Tilt or raise furnace and remove
4 screws
holding
bottom
plate. (See Fig. 22.)
2. Remove
bottom
plate.
3. Remove
bottom
closure
panel.
4. Reinstall
bottom
plate and screws.
Horizontal
Installation
NOTE:
The furnace
nmst be pitched
forward
as shown
in Fig. 23
for proper
condensate
drainage.
The furnace
can be installed
horizontally
in an attic or crawlspace
on either the left-hand
(LH) or right-hand
(RH) side. The furnace
can be hung
from
floor joists,
rafters or trusses
or installed
on a
non-combustible
platform,
blocks,
bricks or pad.
Platform
Furnace
Support
Construct
working
platform
at location
where
all required
furnace
clearances
are met. (See Table 2 and Fig. 27.) For furnaces
with
1-in.
(25
ram)
clearance
requirement
on side,
set furnace
on
non-combustible
blocks,
bricks
or angle
iron.
For crawlspace
installations,
if the furnace
is not suspended
from
the floor joists,
the ground
underneath
furnace
must be level and the furnace
set on
blocks
or bricks.
Suspended
Furnace
Support
The
furnace
must
be supported
under
the
entire
length
of the
furnace
with
threaded
rod and angle iron.
(See Fig. 28.) Secure
angle iron to bottom
of furnace
as shown.
Roll-Out
Protection
Provide
a minimum
12-in.
x 22-in.
(305 x 559 ram) piece of sheet
metal
for flame
roll-out
protection
in front
of burner
area for
furnaces
closer than 12-in.
(305 ram) above the combustible
deck
or suspended
furnaces
closer than 12-in.
(305 ram) to joists.
The
sheet metal
MUST
extend underneath
the furnace
casing
by 1-in.
(25 ram) with the door removed.
The bottom
closure
panel
on furnaces
of widths
17-1/2-in.
(445
ram)
and larger
may be used for flame roll-out
protection
when
bottom
of furnace
is used for return air connection.
See Fig. 27 for
proper
orientation
of roll-out
shield.
Supply
Air
Connections
For a furnace not equipped
with a cooling
coil, the outlet duct shall
be provided
with
a removable
access panel.
This opening
shall be
accessible
when
the furnace
is installed
and shall be of such a size
that the heat exchanger
can be viewed
for possible
openings
using
light
assistance
or a probe
can be inserted
for sampling
the air
stream.
The cover attachment
shall prevent
leaks.
Connect
supply-air
duct to flanges
on furnace
supply-air
outlet.
Bend
flange
upward
to 90 ° with wide
duct pliers.
(See Fig. 20.)
The
supply-air
duct
must
be connected
to ONLY
the
furnace
supply-outlet-air
duct
flanges
or air
conditioning
coil
casing
(when
used).
DO
NOT
cut main
furnace
casing
side
to attach
supply
air duct, humidifier,
or other
accessories.
All accessories
MUST
be connected
to duct external
to furnace
main casing.
Return
Air
Connections
The return-air
duct must be connected
to bottom
of the furnace.
The side of casing that faces downward
may also be used for return
air connection.
A combination
of the
bottom
and downward
facing
side may also be used.
The side of the casing
cannot
be
used as a return air connection.
Bypass
humidifier
may be attached
into unused
return air side of the furnace
casing.
(See Fig. 26.)
Bottom
Return
Air Inlet
These
furnaces
are shipped
with bottom
closure
panel installed
in
bottom
return-air
opening.
Remove
and discard
this panel when
bottom
return air is used. To remove
bottom
closure
panel, perform
the following:
21
ii

Advertisement

loading