Download Print this page

Carrier 59SP5A Installation, Start-Up, Operating And Service And Maintenance Instructions page 32

100 series

Advertisement

alternate
power supply must generate
the same voltage,
phase,
and
frequency
(Hz) as shown
in Table 9 or the furnace
rating plate.
Power
from an alternate
power
supply
that is non-sinusoidal
may
damage
the furnace
electronics
or cause erratic operation.
Contact the alternate power supply manufacturer for specifications
and details,
UNIT SIZE
Table 9 - Electrical
Data
VOLTS-
HERTZ-
PHASE
115-60-1
115-60-1
115-60-1
115-60-1
115-60-1
OPERATING
VOLTAGE
RANGE*
Maximum*
Minimum*
127
104
127
104
127
104
127
104
127
104
MAXIMUM
UNIT
AMPS
6.8
8.4
8.4
10.9
10.9
UNIT
AMPACITY#
40,000
11.0
60,000
13.0
80,000
13.0
100,000
16.1
120,000
16.1
* Permissible limits of the voltage range at which the unit operates
satisfactorily.
MINIMUM
MAXIMUM
WIRE
WIRE
SIZE
LENGTH
AWG
FT (M):_
14
33 (10.0)
14
26 (8.5)
14
28 (8.5)
12
35 (10.6)
12
35 (10.6)
MAXIMUM
FUSE
OR CKT
BKR
AMPSt
15
15
15
2O
2O
# Unit ampacity = 125 percent of largest operating component's
full load amps plus 100 percent of all other potential operating
components'
(EAC, humidifier,
etc.) full load amps.
1"Time-delay
type is recommended.
_Length
shown is as measured
one way along wire path between furnace and service panel for maximum
2 percent voltage drop.
GROUND--
J-BOX
LOCATIONS
Fig. 31 - Installing
J-Box
(When
Used)
Al1299
NEUTRAL
ELECTRIC
DISCONNECT
SWITCH
®
Al1146
Fig.
32 - Field-Supplied
Electrical
Box
on Furnace
Casing
32

Advertisement

loading