Download Print this page

Carrier 59SP5A Installation, Start-Up, Operating And Service And Maintenance Instructions page 29

100 series

Advertisement

GAS PIPING
FIRE
OR EXPLOSION
HAZARD
Failure
to follow
this warning
could
result
in personal
iniury,
death, and/or property
damage.
Never
purge
a gas line into a combustion
chamber.
Never
test for gas leaks with
an open
flame. Use a commercially
available
soap solution
made specifically
for the detection
of leaks to check
all connections.
A fire or explosion
may
result
causing
property
damage,
personal
iniury
or loss of
life.
FIRE
OR EXPLOSION
HAZARD
A failure
to follow
this warning
could
result
in personal
iniury, death, and/or property
damage.
If local
codes
allow
the use
of a flexible
gas
appliance
connector,
always
use a new listed connector.
Do not use a
connector
which
has
previously
served
another
gas
appliance.
Black
iron pipe shall be installed
at the furnace
gas control
valve and extend
a minimum
of 2-in.
(51 mm)
outside
the furnace.
FIRE
OR EXPLOSION
HAZARD
Failure
to follow
this warning
could
result
in personal
injury,
death, and/or property
damage.
Use proper
length
of pipe
to avoid
stress
on gas control
manifold
and gas valve.
FIRE
OR EXPLOSION
HAZARD
Failure
to follow
this warning
could
result
in personal
injury,
death, and/or property
damage.
Gas valve
inlet and/or
inlet pipe must remain
capped
until
gas supply line is permanently
installed
to protect
the valve
from moisture
and debris. Also, install a sediment
trap in the
gas supply piping
at the inlet to the gas valve.
Gas piping must be installed in accordance with national and local
codes. Refer to current edition of NFGC in the U.S.A.
Refer to
current edition of CAN/CSA B149.1
in Canada.
Installations
must be made in accordance
with all authorities
having jurisdiction.
If possible, the gas supply line should be a
separate line running directly from meter to furnace.
NOTE:
Use a back-up wrench on the inlet of the gas valve when
connecting the gas line to the gas valve.
NOTE:
In the state of Massachusetts:
1. Gas supply connections MUST be performed by a licensed
plumber or gas fitter.
2. When flexible connectors are used, the maximum length
shall not exceed 36 in. (915 mm).
3. When lever handle type manual equipment shutoff valves
are used, they shall be T-handle valves.
4. The use of copper tubing for gas piping is NOT approved
by the state of Massachusetts.
Refer to Table 8 for recommended
gas pipe sizing. Risers must be
used to connect to furnace and to meter. Support all gas piping
with appropriate straps, hangers, etc. Use a minimum of 1 hanger
every 6 ft. (1.8 M). Joint compound (pipe dope) should be applied
sparingly and only to male threads of joints. Pipe dope must be
resistant to the action of propane gas.
FURNACE
DAMAGE
HAZARD
Failure to follow this caution
may result in furnace damage.
Connect
gas pipe
to furnace
using
a backup
wrench
to
avoid damaging
gas controls
and burner
misalignment.
An accessible
manual
equipment
shutoff valve MUST
be installed
external
to furnace casing
and within
6 ft. (1.8 M) of furnace.
Install
a sediment
trap in riser leading
to furnace
as shown
in Fig.
30. Connect
a capped
nipple
into lower end of tee. Capped
nipple
should
extend
below
level of furnace
gas controls.
Place a ground
joint union between
furnace
gas control
valve and exterior
manual
equipment
gas shutoff valve.
A l/8-in.
(3 mm) NPT plugged
tapping,
accessible
for test gauge
connection,
MUST
be
installed
immediately
upstream
of gas
supply
connection
to
furnace
and
downstream
of
manual
equipment
shutoff valve.
Piping
should
be pressure
and leak tested
in accordance
with the
current
addition
of the
NFGC
in the United
States,
local,
and
national
plumbing
and
gas
codes
before
the furnace
has been
connected.
Refer
to current
edition
of NSCNGPIC
in Canada.
After
all connections
have been made,
purge
lines and check
for
leakage
at furnace
prior to operating
furnace.
NOTE:
The
furnace
gas
control
valve
inlet
pressure
tap
connection
is suitable
to use as test gauge
connection
providing
test pressure
DOES
NOT
exceed
maximum
0.5 psig (14-in.
w.c.)
stated
on gas control
valve. (See Fig. 51.)
If pressure
exceeds
0.5 psig (14-in.
w.c.), gas supply
pipe must be
disconnected
from
furnace
and capped
before
and during
supply
pipe pressure
test. If test pressure
is equal to or less than 0.5 psig
(14-in.
w.c.), turn off electric
shutoff
switch located
on furnace
gas
control
valve
and
accessible
manual
equipment
shutoff
valve
before
and during
supply
pipe pressure
test. After all connections
have been made, purge lines and check for leakage
at furnace
prior
to operating
furnace.
The
gas
supply
pressure
shall
be
within
the
maximum
and
minimum
inlet supply
pressures
marked
on the rating
plate with
the furnace burners
ON and OFF.
Some
installations
require
gas entry
on right
side of furnace
(as
viewed
in upflow).
(See Fig. 29.)
Gas Pipe Grommet
For direct vent (2-pipe)
applications,
the knockout
for the gas pipe
must be sealed
to prevent
air leakage.
Remove
the knockout,
install
the
grommet
in
the knockout,
then
insert
the gas
pipe.
The
grommet
is included
in the loose parts bag. See Fig. 29.
29

Advertisement

loading