Download Print this page

Carrier 59SP5A Installation, Start-Up, Operating And Service And Maintenance Instructions page 57

100 series

Advertisement

START-UP,
ADJUSTMENT,
AND SAFETY
CHECK
General
1. Furnace
must
have a 115-v power
supply
properly
connec-
ted and grounded.
NOTE:
Proper
polarity
must
be maintained
for l15-v
wiring.
Control
status indicator
light flashes
rapidly
and furnace
does not
operate
if polarity
is incorrect.
2. Thermostat
wire
connections
at terminals
R, W, G, and
Y/Y2
must be made
at 24-v terminal
block
on furnace con-
trol.
3. Natural
gas service
pressure
must not exceed
0.5 psig (14-
in. w.c.), but must be no less than 0.16 psig (4.5-in.
w.c.).
4. Blower
door must be in place to complete
l15-v
electrical
circuit to furnace.
UNIT
OPERATION
HAZARD
Failure to follow
this caution
may result in intermittent
unit
operation
or performance
satisfaction.
These
furnaces
are
equipped
with
a manual
reset
limit
switch
in burner
assembly.
This switch
opens and shuts off
power
to the gas valve
is an overheat
condition
(flame
rollout)
occurs
in burner
assembly.
Correct
inadequate
combustion-air
supply
or
improper
venting
condition
before resetting
switch.
DO NOT jumper
this switch.
Before
operating
furnace,
check flame rollout
manual
reset switch
for continuity.
If necessary,
press button
to reset switch.
EAC-I
terminal
is energized
whenever
blower
operates.
HUM
terminal
is only energized
when blower
is energized
in heating.
Prime Condensate
Trap with Water
[]NIT
OPERATION
HAZARD
Failure to follow
this caution
may result in intermittent
unit
operation
or performance
satisfaction.
Condensate
trap must be PRIMED
or proper
draining
may
not occur.
The condensate
trap has two internal
chambers
which
can ONLY
be primed
by pouring
water
into
the
inducer
drain side of condensate
trap.
1. Remove
upper and middle
collector
box drain plugs oppos-
ite of the condensate
trap.
(See Fig. 57.)
2. Connect
field-supplied
1/2-in.
(13 mm)
OD tube to upper
collector
box drain connection.
3. Insert field-supplied
funnel into tube.
4. Pour one quart of water into funnel/tube.
Water should
run
through
collector
box, overfill
condensate
trap, and flow in-
to open field drain.
5. Remove
funnel;
replace collector
box drain plug.
6. Connect
field-supplied
l/2-in.
(13 mm) OD tube to middle
collector
box drain port.
7. Pour one quart of water into funnel/tube.
Water should
run
through
collector
box, overfill
condensate
trap, and flow in-
to open field drain.
8. Remove
funnel and tube from collector
box and replace
col-
lector box drain plug.
Purge
Gas
Lines
If not previously done, purge the lines after all connections have
been made and check for leaks,
FIRE
OR EXPLOSION
HAZARD
Failure
to follow
this
warning
could
result
in personal
iniury, death, and/or property
damage.
Never
purge
a gas line into a combustion
chamber.
Never
test for gas leaks with an open
flame. Use a commercially
available
soap solution
made
specifically
for the detection
of leaks to check
all connections.
A fire or explosion
may
result
causing
property
damage,
personal
iniury
or loss of
life.
Adjustments
FIRE
HAZARD
Failure
to follow
this
warning
could
result
in personal
iniury, death and/or property
damage.
DO NOT
bottom
out gas valve
regulator
adjusting
screw.
This can result
in unregulated
manifold
pressure
and result
in excess overfire
and heat exchanger
failures.
FURNACE
DAMAGE
HAZARD
Failure
to follow
this caution
may result
in reduced
furnace
life.
DO
NOT
redrill
orifices.
Improper
drilling
(burrs,
out-of-round
holes,
etc.) can cause
excessive
burner
noise
and misdirection
of burner
flames.
This can result
in flame
impingement
of heat exchangers,
causing
failures.
(See Fig.
52.)
For proper
operation
and long term reliability,
the Furnace
input
rate must be within
+2 percent
of input rate on furnace
rating plate.
The gas input
rate on rating plate is for installations
at altitudes
up
to 2000 ft. (609.6M).
In the USA.,
the input rating for altitudes
above 2000 ft. (609.6M)
must be reduced
by 2 percent
for each 1000 ft. (304.8M)
above sea
level. Refer to Table
18.
In Canada,
the
input
rating
must
be derated
by 5 percent
for
altitudes
of 2000
ft. (609.6M)
to 4500
ft. (1371.6M)
above
sea
level.
To adjust
manifold
pressure
to obtain
the proper
input
rate, first,
determine
if the furnace
has the correct
orifice
installed.
At higher
altitudes
or different
gas heat
contents,
it may be
necessary
to
change
the factory
orifice
to a different
orifice.
Tables have been
provided
in the
furnace
installation
instructions
to match
the
required
orifice
to the manifold
pressure
to the heat content
and
specific
gravity
of the gas. To do this:
a. Obtain average yearly gas heat value (at installed
altitude)
from local gas supplier.
b. Obtain average
yearly gas specific gravity
from local gas
supplier.
c. Find installation
altitude
in Table 20.
d. Find closest
natural gas heat value and specific
gravity in
Table 20.
57
g

Advertisement

loading