NOTES FOR THERMOSTAT
WIRING
DIAGRAMS
1. Heat pump MUST
have a high pressure
switch for dual fuel applications.
2. Refer to outdoor
equipment
Installation
Instructions
for additional
information
and setup procedure.
3. If the heat pump date code is 1501E
or earlier, select the "ZONE"
position
on the two speed heat pump control.
Heat pumps with date
code 1601E
and later do not have or require
a "ZONE"
selection.
4. Outdoor
Air Temperature
Sensor must be attached
in all dual fuel applications.
5. Configure
the thermostat
for air conditioner
installations.
Refer to thermostat
instructions.
6. Configure
thermostat
for heat pump installations.
Refer to thermostat
instructions.
7. Configure
thermostat
for single-stage
compressor
operation.
Refer to thermostat
instructions.
8. Configure
thermostat
for two-stage
compressor
operation.
Refer to thermostat
instructions.
9. Configure
thermostat
for Dual Fuel Operation.
Refer to thermostat
instructions.
10. NO connection
should be made to the furnace
HUM terminal
when using a thermostat
with a 24 volt humidifier
output.
11. The RVS Sensing
terminal
"L" should
not be connected.
This is used internally
to sense defrost
operation.
12. If thermostat
has internal
control
of heat pump balance
point,
DO NOT
SELECT
the "FURNACE
INTERFACE"
or "BALANCE
POINT"
option on the two-speed
heat pump control
board. Refer to thermostat
instructions.
13. The RVS Sensing
terminal
"L" should
not be connected.
This is internally
used to sense defrost
operation.
14. Configure
Dehumidify
function
to remove
24 VAC from Dehum
terminal
on a demand
to dehumidify.