Download Print this page

Carrier 59SP5A Installation, Start-Up, Operating And Service And Maintenance Instructions page 59

100 series

Advertisement

ELECTRICAL OPERATION
HAZARD
Failure tofollow this warning could result in personal
injury
ordeath.
Disconnect
115v e lectrical
power before changing
speed tap.
FIRE HAZARD
Failure
t o follow
this warning
could
result
in personal
iniury, death, and/or property
damage.
Reinstall
manifold
pressure
tap plug in gas valve to prevent
gas leak.
Table 16 - Blower
Speed
Taps
FACTORY ATTACHED
COLOR
SPEED
TO:
Gray
5
Cool
Yellow
4
Spare
Blue
3
Heat
Orange
2
Spare
Fled
1
LO HT/Cont. Fan
Read
following
caution
before
changing
taps).
[]NIT
DAMAGE
HAZARD
To
avoid
operating
outside
the
rise
range
and
avoid
component
damage:
1. NEVER
connect
Speed Tap 1 (Red) wire to "HEAT."
2.
NEVER
connect
Speed
Tap 2 (Orange)
wire to "HEAT"
on all models.
To change
blower
motor
speed
selections
for
heating
mode,
remove
blower
motor lead from control
HEAT ternfinal.
(See Fig.
35) Select desired
blower
motor speed lead from one of the other
motor
leads
and relocate
it to HEAT ternfinal.
(See Table
16 for
lead
color
identification.)
Reconnect
original
lead
on SPARE
ternfinal.
Adjust
Blower
Off Delay (Heat Mode)
The blower
off delay has four adjustable
settings
from 90 sec to
180 sec. (See Table 17.)
The blower
off delay jumpers
are located
on the furnace
control
(See Fig. 35 and Fig. 63.)
To change the
blower
off delay setting,
move
the jumper
from one set of pins on
the control
to the pins used
for the desired
blower
off delay.
Factory
blower
off delay setting is 120 sec.
Table 17 - Blower
Off Delay Jumper
Positions
PINS
1 AND 2
2 AND 3
3 AND 4
4 AND 5
Time (in sec.)
90
120
150
180
Adjust
Cooling
Airflow
The cooling
airflow can be set from
the remaining
blower
speed
taps. Refer to the Air Delivery
Tables in these instructions.
Adjust Continuous
Fan Airflow
The Continuous
Fan airflow can be set from the remaining
blower
speed taps. Refer
to the Air Delivery
Tables in these instructions.
The Continuous
Fan speed can be changed to any other speed tap
by toggling
the Fan switch
at the thermostat.
See the Sequence
of
Operation
for details.
FURNACE
OVERHEATING
HAZARD
Failure to follow
this caution
may result in reduced
furnace
life.
Recheck
temperature
rise. It nmst be within linfits specified
on the
rating
plate.
Recommended
operation
is at the
nfid-point
of rise range or slightly
above.
Adjust Thermostat
Heat Anticipator
When
using
a non-electronic
thermostat,
the
thermostat
heat
anticipator
must
be set to match
the amp draw of the electrical
components
in R-W
circuit.
Accurate
amp draw readings
can be
obtained
at the thermostat
subbase
terminals
R and W.
Fig. 53
illustrates
the easy method
of obtaining
actual amp draw.
The amp
reading
should be taken after blower
motor has started and furnace
is heating.
Connect
ammeter wires
as shown
in Fig.
53.
The
thermostat
anticipator should not be in the circuit while
measuring
current.
If thermostat
has no subbase,
the thermostat
must
be
disconnected
from
R and W wires
during
current measurement.
See
thermostat
manufacturer's
instructions
for
ac[iusting
heat
anticipator and for varying heating
cycle length.
For an electronic
thermostat,
set cycle rate for 3 cycles per hr.
Check Safety Controls
The flame sensor,
gas valve,
and pressure
switch
were all checked
in the Start-up
procedure
section as part of normal
operation.
1. Check Main Linfit Switch
This control
shuts off combustion
system
and energizes
air-
circulating
blower
motor, if furnace
overheats.
By using this
method
to check linfit control,
it can be established
that lim-
it is functioning
properly
and will operate
if there is a re-
stricted
return-air
supply
or motor
failure.
If linfit control
does not function
during
this test, cause nmst be determined
and corrected.
a. Run furnace
for at least 5 nfinutes.
b. Gradually
block off return air with a piece of cardboard
or
sheet metal until the limit trips.
c. Unblock
return air to pernfit normal circulation.
d.
Burners
will re-light
when furnace
cools down.
2. Check Pressure
Switch(es)
This control
proves operation
of the draft inducer blower.
a. Turn off 115-v
power to furnace.
b. Disconnect
inducer
motor lead wires from wire harness.
c. Turn on 115-v
power to furnace.
d. Set thermostat
to "call for heat" and wait 1 minute.
When
low pressure
switch
is functioning
properly,
hot surface
igniter
should
NOT
glow
and control
diagnostic
light
flashes
a status code 31. If hot surface igniter glows when
inducer
motor is disconnected,
shut down furnace immedi-
ately.
e. Deternfine
reason
low pressure
switch
did not function
properly
and correct
condition.
f. Turn off 115-v
power to furnace.
59
g

Advertisement

loading