6-2. Outdoor Unit (Parts Ratings)
RAV-SP1104AT-E, RAV-SP1104ATZ-E, RAV-SP1104ATZG-E
RAV-SP1404AT-E, RAV-SP1404ATZ-E, RAV-SP1404ATZG-E
No.
Parts name
1
Compressor
2
Outdoor fan motor
3
Reactor
4
4-way valve coil
5
PMV coil
6
P .C. board
7
Fuse (Mounted on P .C. board)
8
Fuse (Mounted on P .C. board)
9
Fuse (Mounted on P .C. board)
10
Outdoor temp. sensor (TO sensor)
11
Heat exchanger sensor (Te sensor)
12
Discharge temp. sensor (Td sensor)
13
Heat exchanger mid. Temp sensor (TL sensor)
14
Compressor thermo. (Protection)
RAV-SP404AT-E, RAV-SP404ATZ-E, RAV-SP404ATZG-E
RAV-SP454AT-E, RAV-SP454ATZ-E, RAV-SP454ATZG-E
No.
Parts name
1
Fan motor
2
Compressor
3
Reactor
4
Outdoor temp. sensor (To sensor)
5
Heat exchanger sensor (Te sensor)
6
Suction temp. sensor (Ts sensor)
7
Discharge temp. sensor (Td sensor)
8
Fuse (Switching power (Protect))
9
Fuse (Inverter, input (Current protect))
10
4-way valve solenoid coil
11
Compressor thermo. (Protection)
12
Coil (Pulse Motor Valve)
6-3. Accessory Separate Sold Parts
RBC-U31PG (W, WS)-E (Ceiling panel), RBC-U31PGS (W, WS)-E (Ceiling panel)
RAV-SM564UT-E, RAV-SM804UT-E, RAV-SM1104UT-E, RAV-SM1404UT-E, RAV-SM1604UT-E
No.
Parts name
1
Motor-louver
2
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
– 45 –
www.heronhill.co.uk
Type
DA422A3F-25M
ICF-280-A100-1
Output 100W
CH-62
5.7mH, 18.5A
VHV-01AP552B1
AC240V
UKV-A038
DC12V
MCC-1571
AC220 – 240V
—
AC250V, 25A
—
AC250V, 10A
—
AC250V, 3.15A
—
10 kΩ at 25°C
—
10 kΩ at 25°C
—
50 kΩ at 25°C
—
10 kΩ at 25°C
US-622
OFF: 125 ± 4°C, ON: 90 ± 5°C
Type
ICF-140-43-4R
Output (Rated) 43W
DA150A1F-20F
3 phase, 4P, 1100W
CH-57
10mH, 16A
—
10 kΩ at 25°C
—
10 kΩ at 25°C
—
10 kΩ at 25°C
—
50 kΩ at 25°C
—
T3.15A, AC 250V
—
AC240V
STF-01AJ502E1
US-622
OFF: 125 ± 4°C, ON: 90 ± 5°C
CAM-MD12TF-6
Type
MP24ZN3N
DC 12 V
Revised 2: Jun., 2008
Specifications
—
Specifications
—
—
Specifications
Fax: 01823 665807