Toshiba RAV-SM564UT-E Service Manual page 194

Hide thumbs Also See for RAV-SM564UT-E:
Table of Contents

Advertisement

No.
Part name
1. Detachment
Fan motor
7
1) Perform works 1. of 2 , 1. of 3 , and 1. of 6 .
2) Remove lead wires which are connected to the
following connectors of P .C. board assembly.
NOTE)
Unlock locks of the housing, and then remove the
connectors.
CN333 : Fan motor power supply (5P: White)
CN334 : Detection of fan motor (3P: White)
Remove tie wrap which fixes lead wires.
3) Remove the noise filter from lead wire to detect fan
motor position.
4) Take off screws of fan motor fixing bracket.
Earth wires of the motor are tightened together.
(Ø5 × 10, 2 pcs)
Remove tie wrap which fixes the lead wires.
5) Remove fixing bracket of the fan motor by holding it
with hands so that the fan motor does not fall down.
2. Attachment
1) Mount the fan motor as before in order, Fan motor
→ Fixing bracket of fan motor → Noise filter → Lead wire process → E-cover.
NOTE)
Check there is no missing or poor contact of the connectors. Check also that the multi blade
fan turns surely and smoothly, and check together-tightening of motor earth.
1. Detachment
Under panel
8
Drain pan
1) Take off the drain cap and drain the drain water
assembly
accumulated in the drain pan assembly.
In case of natural drain model, drain the drain water
by taking off hose band and drain hose.
NOTE)
When taking off drain cap and drain hose, be sure
receive drain water in a bucket, etc.
2) Take off screws fixing the under panel while holding
it to remove. (Ø4 × 10, 8 pcs)
NOTE)
Be careful that sheeting metal does not fall when
removing the under panel.
3) Pull out the drain pan assy. by holding handle at
lower part.
NOTE)
When pulling out the drain pan assy, never pull out the
drain socket by drawing it with hands. If doing so, water
leak may be caused.
4) Pull out it to some extent, lay hand on the bump at
suction side, and then remove the drain pan assembly.
2. Attachment
1) Hook and attach the drain pan assy. to the flange at
discharge side, and then push in.
2) Using screws taken off in procedure 1. 2) of 8 ,
attach under panel by holding with hands.
3) Attach drain cap, hose band, and drain hose as before,
which were taken off in procedure 1. 1) of 8 .
NOTE)
Finally, be sure to check there is no water leakage from
each attached part.
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
Procedure
– 194 –
www.heronhill.co.uk
Remarks
Earth lead
Earth lead
Drain cap or drain hose
Under panel
Under panel
Drain pan assembly
Drain pan assemb
ain pan assembly
NO GOOD
Never hold and pull
the drain socket.
Fax: 01823 665807

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents