4. Outdoor fan control
W1
W2
SP40, SP45
200
300
1) Cooling fan control

The outdoor fan is controlled by TE, TD, and TO sensors and also revolution frequency of the operation.
The outdoor is controlled by every 1 tap of DC fan control (15 taps).
Only during 60 seconds after the operation has started, the fan is fixed with the maximum fan tap
which corresponds to the zone in the following table.
After then the fan is controlled by TE sensor temperature.
ƒ
Considering a case that TE sensor has come out of the holder, the fan is controlled so that revolution
frequency of the fan increases regardless of TE if temperature of TD sensor has risen.
TE [˚C]
32
29
Temp. range
38°C ≤ TO
32 ≤ TO < 38°C
15 ≤ TO < 32°C
5 ≤ TO < 15°C
1 ≤ TO < 5°C
–5 ≤ TO < 1°C
TO < –5°C
TO error
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
Allocations of fan tap revolutions [rpm]
W3
W4
W5
W6
350
410
480
500
+1 tap/20 seconds
rpm hold
–1 tap/20 seconds
f < 34.1Hz
Min.
Max.
W6
W5
W3
W2
W1
W1
OFF
W1
www.heronhill.co.uk
W7
W8
W9
WA
560
640
670
700
Operation with WE
TD [˚C]
85
80
75
65
34.1Hz ≤ ≤ ≤ ≤ ≤ f < 58.6Hz
Min.
Max.
WB
W8
WD
WA
W7
WC
W7
W5
W9
W5
W4
W7
W3
W3
W5
W2
W2
W4
OFF
W3
WF
W1
WF
– 84 –
WB
WC
WD
WE
750
800
800
840
"WF"
Operation with
maximum tap in
each zone
Usual fan control
58.6Hz ≤ ≤ ≤ ≤ ≤ f
Min.
Max.
WA
WF
W9
WF
W7
WB
W6
W9
W4
W7
W3
W5
W1
W4
W1
WF
Fax: 01823 665807
WF
840