[F02 error]
Is connection of TC sensor connector
(CN101 on Indoor P.C. board) correct?
YES
Are characteristics of
TC sensor resistance value normal?
YES
Check indoor P.C. board (MCC-1570).
Defect → Replace
[F01 error]
Is connection of TCJ sensor connector
(CN102 on Indoor P.C. board) correct?
YES
Are characteristics of
TCJ sensor resistance value normal?
YES
Check indoor main P.C. board (MCC-1570).
Defect → Replace
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
NO
NO
∗ Refer to TC sensor
(Temperature-Resistance value characteristic table)
NO
NO
∗ Refer to Characteristics-2.
– 133 –
www.heronhill.co.uk
<In case of SP40, SP45>
Correct connection of connector.
Replace TC sensor.
Correct connection of connector.
Replace TCJ sensor.