13-5. Confirmation of Indoor Unit No. Position

1. To know the indoor unit addresses though position of the indoor unit body is recognized
• In case of individual operation (Wired remote controller : indoor unit = 1 : 1)
(Follow to the procedure during operation)
<Procedure>
1
ON / OFF
Push
button if the unit stops.
2
UNIT LOUVER
Push
button.
1-1
Unit No.
is displayed on LCD.
(It disappears after several seconds.)
The displayed unit No. indicate line address and
indoor unit address.
(When other indoor units are connected to the
identical remote controller (Group control unit), other
unit numbers are also displayed every pushing
UNIT LOUVER
button.
2. To know the position of indoor unit body by address
• To confirm the unit No. in the group control
(Follow to the procedure during operation) (in this procedure, the indoor units in group control stop.)
<Procedure>
The indoor unit numbers in the group control are
successively displayed, and fan, louver, and drain pump
of the corresponding indoor unit are turned on.
(Follow to the procedure during operation)
1
VENT
TEST
Push
and
buttons simultaneously for
4 seconds or more.
• Unit No.
is displayed.
• Fans and louvers of all the indoor units in the
group control operate.
2
UNIT LOUVER
Every pushing
in the group control are successively displayed.
• The unit No. displayed at the first time indicates the
master unit address.
• Fan and louver of the selected indoor unit only
operate.
3
TEST
Push
button to finish the procedure.
All the indoor units in the group control stop.
Tel: 01823 665660
Heronhill - for all your Toshiba requirements
button, the unit numbers
– 179 –
www.heronhill.co.uk
TEMP.
TIMER SET
TIME
FILTER
RESET
TEST
SET
CL
<Operation procedure>
1
2
END
TEMP.
TIMER SET
1
TIME
FILTER
RESET
TEST
SET
CL
3
<Operation procedure>
1
2
3
END
Fax: 01823 665807
Revised 2: Jun., 2008
ON / OFF
1
Operation
FAN
MODE
SAVE
VENT
SWING/FIX
UNIT LOUVER
2
ON / OFF
FAN
MODE
SAVE
VENT
SWING/FIX
UNIT LOUVER
2

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents